DS180D6S Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET | |||
|
DIESEL GENERATOR SET
DS180D6S
180 kWe /60 Hz /Standby
208 - 600V
(Reference DP180D6S for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
** UL 2200 Oï¬ered
DS180D6SGA
240V**
1
1.0
60
180
180
750
DS180D6SDA
240V**
1
1.0
60
180
180
750
267
432CSL6210
130 °C/40 °C
12 LEAD ZIG-ZAG
370
432PSL6228
130 °C/40 °C
4 LEAD
CERTIFICATIONS AND STANDARDS
DS180D6SPA
208V**
3
0.8
60
180
225
625
DS180D6SJA
240V**
3
0.8
60
180
225
541
DS180D6SRA
480V**
3
0.8
60
180
225
271
DS180D6SNA
600V**
3
0.8
60
180
225
217
433
431CSL6206
130 °C/40 °C
12 LEAD LOW WYE
433
431CSL6206
130 °C/40 °C
12 LEAD HI DELTA
451
431CSL6204
130 °C/40 °C
12 LEAD HI WYE
510
431PSL6243
130 °C/40 °C
4 LEAD WYE
//â Emissions â EPA Tier 3 Certiï¬ed
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
//â Seismic Certification â Optional
â IBC Certiï¬cation
â OSHPD Pre-Approval
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
|
▷ |