English
Language : 

DP275D6S Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
DIESEL GENERATOR SET
DP275D6S
275 kWe /60 Hz /Prime
208 - 600V
(Reference DS300D6S for Standby Rating Technical Data)
SYSTEM RATINGS
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
** UL 2200 Offered
DP275D6SPA
208V**
3
0.8
60
275
343
954
DP275D6SJA
240V**
3
0.8
60
275
343
827
DP275D6SVA
380V
3
0.8
60
275
343
522
930
433CSL6216
105 °C/40 °C
12 LEAD LOW WYE
930
433CSL6216
105 °C/40 °C
12 LEAD HI DELTA
640
433CSL6216
105 °C/40 °C
12 LEAD HI WYE
CERTIFICATIONS AND STANDARDS
DP275D6SWA
440V
3
0.8
60
275
343
451
DP275D6SRA
480V**
3
0.8
60
275
343
413
860
433CSL6216
105 °C/40 °C
12 LEAD HI WYE
1238
432CSL6216
105 °C/40 °C
12 LEAD HI WYE
DP275D6SNA
600V**
3
0.8
60
275
343
331
720
432PSL6246
105 °C/40 °C
4 LEAD WYE
//  Emissions – EPA Tier 3 Certified
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 75%.