English
Language : 

DP1955D6S Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL POWER MODULE
DIESEL POWER MODULE
DP1955D6S / DP2151D5S
Voltages:
2160 kWe / 2700 kVA / 60 Hz / Standby - 480V
1955 kWe / 2443 kVA / 60 Hz / Prime - 480V
1760 kWe / 2200 kVA / 60 Hz / Continuous - 480V
1900 kWe / 2375 kVA / 50 Hz / Standby - 400V
1721 kWe / 2151 kVA / 50 Hz / Prime - 400V
1500 kWe / 1875 kVA / 50 Hz / Continuous 400V
SYSTEM RATINGS
DS2160D6SRW DP1955D6SRW DB1760D6SRW
DS2375D5SFW DP2151D5SFW
DB1875D5SFW
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model
Temp Rise
Connection
480V / 60 Hz
3
0.8
60
2,160
2,700
3,251
5,750
744RDL4056
150 °C/40 °C
4 BAR WYE
480V / 60 Hz
3
0.8
60
1,955
2,443
2,942
5,750
744RDL4056
125 °C/40 °C
4 BAR WYE
480V / 60 Hz
3
0.8
60
1,760
2,200
2,649
5,750
744RDL4056
105 °C/40 °C
4 BAR WYE
400V / 50 Hz
3
0.8
50
1,900
2,375
3,432
4,530
744RDL4056
150 °C/40 °C
4 BAR WYE
400V / 50 Hz
3
0.8
50
1,721
2,151
3,108
4,530
744RDL4056
125 °C/40 °C
4 BAR WYE
400V / 50 Hz
3
0.8
50
1,500
1,875
2,709
4,530
744RDL4056
105 °C/40 °C
4 BAR WYE
CERTIFICATIONS AND STANDARDS
//  Emissions
– Fuel Optimized
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  Container
– CSC Certified
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Permissible average power output during 24 hours of
operation is approved up to 85% for standby rated unit.
- Permissible average power output during 24 hours of
operation is approved up to 75% for prime rated unit.
- Permissible average power output during 24 hours of
operation is approved up to 100% for continuous rated unit.