English
Language : 

ADG0102D Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
DIESEL GENERATOR SET
TYPE ADG102D
99 kVA/Prime/50Hz
(109 kVA/LTP/50Hz)
A TOGNUM GROUP BRAND
Optional equipment shown. Standard equipment may vary.
BENEFITS
// Most compact design
// Air cooled engine — trouble-free cooling system
// Lowest maintenance cost
// High user-friendlyness
SYSTEM RATINGS➀
Prime (LTP)➁
Voltage (L-L)
Phase
PF
Hz
kWe
kVA
AMPS
Generator model
Temp rise
Load acceptance
ADG102D
380V
3
0.8
50
79.2 (87.2)
99 (109)
150
ACG-0102-4-400
125°C (150°C)
66%
ADG102D
400V
3
0.8
50
79.2 (87.2)
99 (109)
143
ACG-0102-4-400
125°C (150°C)
66%
ADG102D
415V
3
0.8
50
79.2 (87.2)
99 (109)
138
ACG-0102-4-400
125°C (150°C)
66%
➀ Power available up to 25°C/100 m
➁ Technical data for prime power