English
Language : 

615-XC6DT2 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
DIESEL GENERATOR SET
615-XC6DT2
615 kWe /60 Hz /Prime
208 - 4160V
(Reference 650-XC6DT2 for Standby Rating Technical Data)
SYSTEM RATINGS
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V**
3
0.8
60
615
768.75
2134
1750
573RSL4033
105 °C/40 °C
12 LEAD LOW WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
240V**
3
0.8
60
615
768.75
1849
1750
573RSL4033
105 °C/40 °C
12 LEAD HI DELTA
380V
3
0.8
60
615
769
1169
1600
574RSL4037
105 °C/40 °C
12 LEAD HI WYE
480V**
3
0.8
60
615
768.75
925
1750
573RSL4033
105 °C/40 °C
12 LEAD HI WYE
600V**
3
0.8
60
615
768.75
740
1350
573RSS4274
105 °C/40 °C
4 LEAD WYE
4160V
3
0.8
60
615
768.75
107
1850
574FSM4358
105 °C/40 °C
6 LEAD WYE
CERTIFICATIONS AND STANDARDS
//  Emissions – EPA Tier 2 Certified
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 75%.