English
Language : 

60-GC6NLT1-STANDBY Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – GAS GENERATOR SET
GAS GENERATOR SET
60-GC6NLT1
60 kWe /60 Hz /Standby
208 - 600V
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
Natural Gas
Ratings: Amps
Natural Gas
Ratings: kW/kVA
LP Gas
Ratings: Amps
LP Gas
Ratings: kW/kVA
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
240V**
1
1.0
60
229
55/55
250
60/60
127
362CSL1606
130 °C/40 °C
12 LEAD ZIG-ZAG
* Consult the factory for alternate configuration.
** UL 2200 Offered
240V**
1
1.0
60
229
55/55
250
60/60
230
362CSL1615
130 °C/40 °C
4 LEAD
208V**
3
0.8
60
240V**
3
0.8
60
480V**
3
0.8
60
208
180
90
60/75
60/75
60/75
208
180
90
60/75
60/75
60/75
200
361CSL1602
130 °C/40 °C
12 LEAD LOW WYE
200
361CSL1602
130 °C/40 °C
12 LEAD HI DELTA
172
361CSL1601
130 °C/40 °C
12 LEAD HI WYE
600V**
3
0.8
60
72
60/75
72
60/75
140
361PSL1633
130 °C/40 °C
4 LEAD WYE
CERTIFICATIONS AND STANDARDS
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  UL 2200 / CSA – Optional
– UL 2200 Listed
– CSA Certified
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for
Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110