English
Language : 

3000-XC6DT2-STANDBY Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET
DIESEL GENERATOR SET
3000-XC6DT2
3000 kWe /60 Hz /Standby
380 - 13.8kV
(Reference 2800-XC6DT2 for Prime Rating Technical Data)
SYSTEM RATINGS
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator
Model*
Temp Rise
Connection
380V
3
0.8
60
3000
3750
5704
4000
1030FDL1110
130 °C/40 °C
6 LEAD WYE
480V**
3
0.8
60
3000
3750
4511
5400
1030FDL1108
130 °C/40 °C
6 LEAD WYE
* Consult the factory for alternate configuration.
** UL 2200 Offered
600V
3
0.8
60
3000
3750
3609
6125
1030FDS1126
130 °C/40 °C
6 LEAD WYE
4160V
3
0.8
60
3000
3750
520
5250
1020FDM1184
130 °C/40 °C
6 LEAD WYE
12470V
3
0.8
60
3000
3750
174
5125
1030FDH1254
130 °C/40 °C
6 LEAD WYE
13200V
3
0.8
60
3000
3750
164
13800V
3
0.8
60
3000
3750
157
5625
6000
1030FDH1254 1030FDH1254
130 °C/40 °C 130 °C/40 °C
6 LEAD WYE 6 LEAD WYE
CERTIFICATIONS AND STANDARDS
//  Emissions – EPA Tier 2 Certified
//  Generator set is designed and manufactured
in facilities certified to standards ISO 9001:2008 and
ISO 14001:2004
//  UL 2200 Listed – Optional
//  Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Verified product design, quality and performance integrity
- All engine systems are prototype and factory tested
//  Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 85%.