English
Language : 

250-JC6DT3 Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL ENGINE-GENERATOR SET
A tognum Group Brand
DIESEL ENGINE-GENERATOR SET
250-JC6DT3
250 ekW / 60 Hz / Standby
220 ekW / 60 Hz / Prime
208 - 600V
System Ratings
Standby
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V**
3
0.8
60
250
312.5
867
520
432CSL6210
130°C/27°C
12 LEAD LOW WYE
240V**
3
0.8
60
250
312.5
752
520
432CSL6210
130°C/27°C
12 LEAD HI DELTA
480V**
3
0.8
60
250
312.5
376
700
432CSL6210
130°C/27°C
12 LEAD HI WYE
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
AMPS
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
208V**
3
0.8
60
220
275
763
520
432CSL6210
105°C/40°C
12 LEAD LOW WYE
240V**
3
0.8
60
220
275
662
520
432CSL6210
105°C/40°C
12 LEAD HI DELTA
480V**
3
0.8
60
220
275
331
700
432CSL6210
105°C/40°C
12 LEAD HI WYE
* The Generator Model Number identified in the table is for standard C Series Configuration. Consult the factory for alternate configuration.
** UL2200 Offered
600V**
3
0.8
60
250
312.5
301
722
432PSL6246
125°C/40°C
4 LEAD WYE
600V**
3
0.8
60
220
275
265
722
432PSL6246
105°C/40°C
4 LEAD WYE