1400-XC6DT2-PRIME Datasheet, PDF (1/4 Pages) MTU Onsite Energy Corporation – DIESEL GENERATOR SET | |||
|
DIESEL GENERATOR SET
1400-XC6DT2
1400 kWe /60 Hz /Prime
380 - 4160V
(Reference 1500-XC6DT2 for Standby Rating Technical Data)
SYSTEM RATINGS
Prime
Voltage (L-L)
Phase
PF
Hz
kW
kVA
Amps
skVA@30%
Voltage Dip
Generator Model*
Temp Rise
Connection
380V
3
0.8
60
1400
1750
2662
3350
744RSL4054
105 °C/40 °C
4 BAR WYE
* Consult the factory for alternate conï¬guration.
** UL 2200 Oï¬ered
480V**
3
0.8
60
1400
1750
2105
3500
742RSL4050
105 °C/40 °C
12 LEAD HI WYE
600V**
3
0.8
60
1400
1750
1684
4800
743RSS4290
105 °C/40 °C
4 BAR WYE
4160V
3
0.8
60
1400
1750
243
3900
743FSM4368
105 °C/40 °C
6 LEAD WYE
CERTIFICATIONS AND STANDARDS
//â Emissions â EPA Tier 2 Certiï¬ed
//â Generator set is designed and manufactured
in facilities certiï¬ed to standards ISO 9001:2008 and
ISO 14001:2004
//â Seismic Certification â Optional
â IBC Certiï¬cation
â OSHPD Pre-Approval
//â UL 2200 / CSA â Optional
â UL 2200 Listed
â CSA Certiï¬ed
//â Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
- Veriï¬ed product design, quality and performance integrity
- All engine systems are prototype and factory tested
//â Power Rating
- Accepts Rated Load in One Step Per NFPA 110
- Permissible average power output during 24 hours of
operation is approved up to 75%.
|
▷ |