MDR-120S Datasheet, PDF (1/2 Pages) MicroPower Direct, LLC – 120W Output Power | |||
|
MDR-120S
Compact, 120W
DIN Rail Mount
AC/DC Power Supply
Electrical Speciï¬cations
Key Features:
⢠120W Output Power
Speciï¬cations typical @ +25°C, 230 VAC input voltage & rated output current, unless otherwise noted. Speciï¬cations subject to change without notice.
Input
Parameter
Conditions
Min. Typ. Max. Units
⢠EN 60950 Approved
Input Voltage Range
85
264
VAC
120
370
VDC
⢠Compact, DIN Rail Case Input Frequency
47
63
Hz
⢠Active PFC
Inrush Current, See Note 1
115 VAC
35
230 VAC
70
A Pk
⢠85-264 VAC Input
⢠TS-35/7.5 or TS-35/15 Rails
⢠Meets EN 55022 B
⢠High Efï¬ciency
Power Factor Correction
Input Under Voltage Shutdown
Start Up Time
Output
115 VAC
0.98
230 VAC
0.96
Start Up 76
Shut Down 67
83
75
VAC
1.5
S
⢠Remote ON/OFF Control Parameter
Output Voltage Accuracy
Conditions
Min. Typ. Max.
±1.0
Units
%
Output Voltage Adjust
±5.0
%
Line Regulation
Load Regulation
VIN = Min to Max
IOUT = 10% to 100%
±0.5
%
±1.0
%
Ripple & Noise (20 MHz)
100
m V P-P
Hold-Up Time
115/230 VAC
25.0
mS
Temperature Coefï¬cient
±0.03
%/°C
Over Temperature Protection
Auto-Recovery
95
°C
Over Voltage Protection
See Note 2
30
VDC
Short Circuit Protection, See Note 3
Continuous (Auto-Recovery)
Overload Protection, See Note 4
General
Auto-Recovery 110
150
%IOUT
Parameter
Conditions
Min. Typ. Max. Units
Isolation Voltage, 60S
Switching Frequency
Input to Output 3,000
Input to ï 1,500
VAC
Output to ï 500
100
kHz
EMI Characteristics, See Note 5
Parameter
Standard
Criteria
Level
Radiated Emissions
EN 55024
Class B
Conducted Emissions
EN 55022
Class B
ESD
EN 61000-4-2
B
±8 kV Air
±6 kV Contact
RS
EN 61000-4-3
A
10V/m
EFT
EN 61000-4-4
B
±4 kV
Surge
EN 61000-4-5
B
±2 kV/ ±4 kV
CS
EN 61000-4-6
A
10 Vrms
PFM
EN 61000-4-8
A
10A/m
MicroPower Direct
292 Page Street
Suite D
Stoughton, MA 02072
USA
Voltage Dips, Interruptions
Environmental
Parameter
Operating Temperature Range
Storage Temperature Range
Cooling
EN 61000-4-11
B
0% - 70%
Conditions
Min. Typ. Max.
Ambient -25 +25 +70
-25
+85
Free Air Convection (See Derating Curve on Page 2)
Units
°C
°C
T: (781) 344-8226
F: (781) 344-8481
E: sales@micropowerdirect.com
W: www.micropowerdirect.com
Humidity
Physical
Case Size
Case Material
Weight
RH, Non-condensing
95
%
See Mechanical Diagram (Page 2)
Heat Resistant Plastic (UL94-V0) and Metal
18.9 Oz (560g)
Reliability Speciï¬cations
Parameter
Conditions
Min. Typ. Max. Units
MTBF
MIL HDBK 217F, 25°C, Gnd Benign 300
kHours
Safety Standards
EN 60950
Safety Class
Class I
www.micropowerdirect.com
|
▷ |