Electrical Specifications
Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
Input
Key Features:
• 75W Output Power
Parameter
Input Voltage Range
Conditions
Min. Typ. Max.
85
264
120
370
Units
VAC
VDC
• DIN Rail Mountable
Input Frequency Range
47
63
Hz
• Universal AC Input
• UL 508 Approved
• Safety Approved
• 12, 24 & 48 VDC Outputs
• Cond./Rad. EMI Class B
• >120 kH MTBF
• LOW COST!
Inrush Current
Leakage Current
Output
Parameter
Output Voltage Tolerance
Voltage Adjustment Range
230 VAC, Cold Start
115 VAC, Cold Start
240 VAC
40
20
1.0
Conditions
Min. Typ. Max.
Note 1
±1.0
12 VDC Output 12
14
24 VDC Output 24
28
A
mA
Units
%
VDC
48 VDC Output 48
53
Line Regulation
±0.5
%
Load Regulation
Iout = 10% to 100%
±1.0
%
Set Up Time
230 VAC, Full Load
115 VAC, Full Load
1,000
1,800
mSec
Rise Time
At Full Load
60
mSec
Hold Time
230 VAC, Full Load
60
115 VAC, Full Load
12
mSec
12 VDC Output
100
Ripple & Noise (Note 2)
24 VDC Output
150 mV Pk-Pk
48 VDC Output
240
Output Power Protection
Note 3 105
150
%
12 VDC Output 15
16.5
Over Voltage Protection (Note 4)
24 VDC Output 30
36
VDC
48 VDC Output 54
60
Over Temperature Protection
Note 5 80 85 90
ºC
Temperature Coefficient
0ºC to 50ºC
±0.03
%/ºC
Switching Frequency
Fixed
50
kHz
General
Parameter
Conditions
Min. Typ. Max. Units
Input - Output 3,000
Isolation Voltage
RoHS Compliant
Input - FG (Frame Ground) 1,500
VAC
Output - FG (Frame Ground) 500
Isolation Resistance (Note 6)
500 VDC 100
MΩ
MicroPower Direct
232 Tosca Drive
Stoughton, MA 02072
USA
Environmental
Parameter
Operating Temperature Range
Storage Temperature Range
Operating Humidity
Conditions
Min. Typ. Max.
Ambient -10 +25 +60
-20
+85
RH, Non-condensing 20
90
Units
ºC
ºC
%
T: (781) 344-8226
F: (781) 344-8481
E: sales@micropowerdirect.com
W: www.micropowerdirect.com
Storage Humidity
Vibration
Physical
Case Size
Case Material
RH, Non-condensing 10
95
%
10 ~ 500 Hz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour
2.18 x 4.93 x 3.94 Inches (55.5 x 125.5 x 100.0 mm)
Aluminum
Connection
Screw Terminal
Weight
21 Oz (0.6 kg)
Reliability Specifications
Parameter
Conditions
Min. Typ. Max. Units
MTBF
MIL HDBK 217F, 25ºC, Gnd Benign 123.1
kHours
Safety Standards
UL 508, UL 60950, EN 60950-1
Safety Approvals
UL, cUL, TUV
EMI Compliance
Compliance to EN55011, EN55022 (CISPR22) Class B
Harmonic Current Compliance
Compliance to EN6100-3-2,-3
EMS Immunity Compliance
EN6100-4-2,3,4,5,6,8,11; ENV50204;EN6100-6-2(EN50082-2) Heavy Ind. Level, criteria A