English
Language : 

DR-120 Datasheet, PDF (1/2 Pages) Total Power International – 120W Single Output Industrial DIN RAIL Power Supply
DR-120 Series
Low Cost, Industrial
120W, DIN Rail Mount
AC/DC Power Supplies
New Industrial
Supplies!!
Electrical Specifications
Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
Input
Key Features:
• 120W Output Power
Parameter
Input Voltage Range
Conditions
Min. Typ. Max.
88
132
AC Input Selected by Switch On Front Panel 176
264
Units
VAC
• DIN Rail Mountable
248
370
VDC
• Selectable AC Input
• UL 508 Approved
• Safety Approved
• 12, 24 & 48 VDC Outputs
• Cond./Rad. EMI Class B
• >136 kH MTBF
Input Frequency Range
Inrush Current
Leakage Current
Output
Parameter
Output Voltage Tolerance
47
63
230 VAC, Cold Start
40
115 VAC, Cold Start
20
240 VAC
3.5
Conditions
Min. Typ. Max.
Note 1
±1.0
Hz
A
mA
Units
%
• LOW COST!
Voltage Adjustment Range
12 VDC Output 12
24 VDC Output 24
14
28
VDC
48 VDC Output 48
53
Line Regulation
±0.5
%
Load Regulation
Iout = 10% to 100%
±1.0
%
Set Up Time
At Full Load
500
mSec
Rise Time
At Full Load
70
mSec
Hold Time
230 VAC, Full Load
36
115 VAC, Full Load
32
mSec
12 VDC Output
80
Ripple & Noise (Note 2)
24 VDC Output
80 mV Pk-Pk
48 VDC Output
100
Output Power Protection
Note 3 105
150
%
12 VDC Output 15
16.5
Over Voltage Protection (Note 4)
24 VDC Output 29
33
VDC
48 VDC Output 58
65
Over Temperature Protection (Note 5)
12 VDC Output 80 85 90
24 & 48 VDC Output 85 90 95
ºC
Temperature Coefficient
0ºC to 50ºC
±0.03
%/ºC
Switching Frequency
Fixed
55
kHz
General
Parameter
Conditions
Min. Typ. Max. Units
Input - Output 3,000
RoHS Compliant Isolation Voltage
Input - FG (Frame Ground) 1,500
VAC
Output - FG (Frame Ground) 500
Isolation Resistance (Note 6)
500 VDC 100
MΩ
MicroPower Direct Environmental
232 Tosca Drive
Parameter
Conditions
Min. Typ. Max. Units
Stoughton, MA 02072
Operating Temperature Range
Ambient -10 +25 +60
ºC
USA
Storage Temperature Range
-20
+85
ºC
Operating Humidity
RH, Non-condensing 20
90
%
T: (781) 344-8226
F: (781) 344-8481
E: sales@micropowerdirect.com
W: www.micropowerdirect.com
Storage Humidity
Vibration
Physical
Case Size
RH, Non-condensing 10
95
%
10 ~ 500 Hz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour
2.60 x 4.93 x 3.94 Inches (65.5 x 125.5 x 100.0 mm)
Case Material
Aluminum
Connection
Screw Terminal
Weight
28 Oz (0.79 kg)
Reliability Specifications
Parameter
Conditions
Min. Typ. Max. Units
MTBF
MIL HDBK 217F, 25ºC, Gnd Benign 136.8
kHours
Safety Standards
UL 508, UL 60950, EN 60950-1
Safety Approvals
UL, cUL, TUV
EMI Compliance
Compliance to EN55011, EN55022 (CISPR22) Class B
Harmonic Current Compliance
Compliance to EN6100-3-2,-3
EMS Immunity Compliance
EN6100-4-2,3,4,5,6,8,11; ENV50204;EN6100-6-2(EN50082-2) Heavy Ind. Level, criteria A