English
Language : 

AD1048F_14 Datasheet, PDF (1/2 Pages) MicroPower Direct, LLC – AD1048FS Series
AD1048FS Series
Low Cost, 36 - 48W
DIN Rail Mount
Single Output
AC/DC Power Supplies
Electrical Specifications
Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
Key Features:
• 36W - 48W Output Power
• DIN Rail Mountable
Input
Parameter
Input Voltage Range
Conditions
Min. Typ. Max.
Universal 100
240
127
370
Units
VAC
VDC
• Universal AC Input
• UL 508 Compliant
Input Frequency
Inrush Current, Cold Start
47
63
Hz
110 VAC
22
A
220 VAC
44
A
• EN60950 Compliant
• 12, 15, 24 & 48 VDC Outputs
• Cond./Rad. EMI Class B
Leakage Current
Output
Parameter
Output Voltage Accuracy
264 VAC
1.0
Conditions
Min. Typ. Max.
±0.5
mA
Units
%
• >170 kH MTBF
• LOW COST!
Output Voltage Adjustment Range
Line Regulation
Load Regulation, See Note 1
±10.0
%
Vin = Min to Max
±1.0
%
Iout = 20% to 100%
±1.0
%
Hold Time
110 VAC, Full Load
10
220 VAC, Full Load
20
mSec
Ripple & Noise, See Note 2
See Model Selection Guide
Output Power Protection
Power Limit 130
160
%
Transient Recovery Time, See Note 3
Transient Response Deviation
50% Load Change
2
5
mS
%
Temperature Coefficient
±0.04 ±0.05 %/ºC
Output Short Circuit
Continuous With Autorecovery
General
Parameter
Conditions
Min. Typ. Max. Units
Input - Output 3,000
Isolation Voltage
Input - FG (Frame Ground) 2,000
VAC
Output - FG (Frame Ground) 500
Isolation Resistance (Note 4)
500 VDC 100
M⍀
Switching Frequency
Fixed
66
kHz
Environmental
Parameter
Conditions
Min. Typ. Max. Units
Operating Temperature Range
Ambient -20 +25 +50
ºC
MicroPower Direct
292 Page Street
Suite D
Stoughton, MA 02072
USA
Storage Temperature Range
Cooling
Humidity
Vibration
Physical
Case Size
-20
+85
ºC
Free Air Convection
RH, Non-condensing
95
%
10 Hz ~ 2 kHz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour
3.54 x 2.54 x 1.77 Inches (90.0 x 64.5 x 45.0 mm)
T: (781) 344-8226
F: (781) 344-8481
E: sales@micropowerdirect.com
Case Material
Connection
Reliability Specifications
Plastic
Screw Terminal
W: www.micropowerdirect.com Parameter
Conditions
Min. Typ. Max. Units
MTBF
MIL HDBK 217F, 25ºC, Gnd Benign 170
kHours
Safety Standards
UL 1950, EN 60950, IEC 60950
EMI Compliance
Compliance to EN55011, EN55022 (CISPR22) Class B
EMS Immunity Compliance
EN6100-4-2,3,4,5,6,8,11 Level 3
www.micropowerdirect.com