English
Language : 

AD1048FS Datasheet, PDF (1/2 Pages) MicroPower Direct, LLC – Very Low Cost, 36 - 48W DIN Rail Mount Single Output AC/DC Power Supplies
AD1048FS Series
Very Low Cost, 36 - 48W
DIN Rail Mount
Single Output
AC/DC Power Supplies
New Industrial
Supplies!!
Key Features:
Electrical Specifications
• 36W - 48W Output Power Specifications typical @ +25°C, nominal input voltage & rated output current, unless otherwise noted. Specifications subject to change without notice.
• DIN Rail Mountable
Input
• Universal AC Input
Parameter
Conditions
Min. Typ. Max. Units
• UL 508 Compliant
• EN60950 Compliant
• 12, 15, 24 & 48 VDC Outputs
• Cond./Rad. EMI Class B
• >170 kH MTBF
• LOW COST!
Input Voltage Range
Input Frequency
Inrush Current, Cold Start
Leakage Current
Output
Universal 100
240
127
370
47
63
110 VAC
22
220 VAC
44
264 VAC
1.8
VAC
VDC
Hz
A
A
mA
Parameter
Conditions
Min. Typ. Max. Units
Output Voltage Accuracy
±0.5
%
Output Voltage Adjustment Range
±10.0
%
Line Regulation
Vin = Min to Max
±1.0
%
Load Regulation (Note 1)
Iout = 20% to 100%
±1.0
%
Hold Time
110 VAC, Full Load
10
220 VAC, Full Load
20
mSec
Ripple & Noise (20 MHz) (Note 2)
See Model Selection Guide
Output Power Protection
Power Limit 130
160
%
Transient Recovery Time (Note 3)
Transient Response Deviation
50% Load Change
2
5
mS
%
Temperature Coefficient
±0.04 ±0.05 %/ºC
Output Short Circuit
Continuous With Autorecovery
General
RoHS Compliant Parameter
Conditions
Min. Typ. Max. Units
Input - Output 3,000
Isolation Voltage
Input - FG (Frame Ground) 2,000
VAC
Output - FG (Frame Ground) 500
MicroPower Direct
292 Page Street
Suite D
Stoughton, MA 02072
USA
Isolation Resistance (Note 4)
Switching Frequency
Environmental
Parameter
Operating Temperature Range
Storage Temperature Range
500 VDC 100
Fixed
66
Conditions
Min. Typ. Max.
Ambient -20 +25 +50
-20
+85
MΩ
kHz
Units
ºC
ºC
T: (781) 344-8226
F: (781) 344-8481
E: sales@micropowerdirect.com
W: www.micropowerdirect.com
Cooling
Humidity
Vibration
Physical
Free Air Convection
RH, Non-condensing
95
%
10 Hz ~ 2 kHz; 2G 10 min./1 Cycle; X, Y, Z axis each 1 hour
Case Size
3.54 x 2.54 x 1.77 Inches (90.0 x 64.5 x 44.0 mm)
Case Material
Plastic
Connection
Screw Terminal
Reliability Specifications
Parameter
Conditions
Min. Typ. Max. Units
MTBF
MIL HDBK 217F, 25ºC, Gnd Benign 170
kHours
Safety Standards
UL 1950, EN 60950, IEC 60950
EMI Compliance
Compliance to EN55011, EN55022 (CISPR22) Class B
EMS Immunity Compliance
EN6100-4-2,3,4,5,6,8,11 Level 3