English
Language : 

TA100W-11 Datasheet, PDF (2/4 Pages) MORNSUN Science& Technology Ltd. – Transducers power supply
Distribution
(Isolators with isolated power
output)
Field Area
Control Area
No-load Voltage
Full-load Voltage
Input Signal
Input Impedance
Output Signal
Ripple & Noise
Load
24V±10%
≥20V
See selection guide
≤2V(Current input @20mA)
≥100KΩ(Voltage input)
See selection guide
≤60m Vp-p
≤500Ω(@maximum output current)
≥1000Ω(@maximum output voltage)
TRANSMISSION CHARACTERISTICS
Zero Offset
0.1%F.S.
Accuracy
0.1%F.S.
Gain Error
0.1%F.S.
Temperature drift coefficient 0.0035%F.S./℃(-25℃~+71℃ Operating temperature range)
ISOLATION CHARACTERISTICS
Electrical Isolation
Three-port isolation (input, output and power supply)
2.0KVAC,3.0KVDC between application field and control cabinet
Isolation Voltage
2.0KVAC,3.0KVDC between signal input or output and power supply
2.0KVAC,3.0KVDC between channels ( multi-channel products )
Test conditions: testing for 1minute, humidity < 70%, leakage current < 1mA
EMC CHARACTERISTICS
RE
EMI
CE
CISPR22/EN55022 CLASS A
CISPR22/EN55022 CLASS A
ESD
IEC/EN61000-4-2 Contact ±4KV / Air ±8KV
IEC/EN61000-4-4 DC Power Port ±2KV
EFT
IEC/EN61000-4-4 I/O Signal Port ±1KV
Surge
IEC/EN61000-4-5 DC Power Port ±1KV /±2KV
IEC/EN61000-4-5 I/O Signal Port ±1KV(Line to GND)
perf. Criteria B
perf. Criteria B
perf. Criteria B
perf. Criteria B
perf. Criteria B
OTHER CHARACTERISTICS
Ambient temperature
Operating temperature range: -25°C ~ +71°C
Transport and storage temperature: -40°C ~ +85°C
Package
35mm DIN-rail package: T-rail card package (DIN50022), pluggable connection pin, thickness 12.50mm
Safety Class
IP20(IEC60529 / EN60529)
Weight
1 input 1 output: about 100g;2 input 2 output & 1 input 2 output: about128g
CONNECTION
1. Connection used dismountable terminals;
2. Cross section area of wiring: 0.5mm2 ~2.5 mm2;
3. The length of bare wire is about 8mm, locked up by the M3 bolt.
Application in industry
In the field application, isolator should not be installed In intrinsically safe area.
Selection guidelines for Isolator or Isolator with isolation power output
1. Take care of output independence of isolator or isolator with isolation power output and loop resistance to make sure the its output voltage meets
the minimum operation voltage requirement of field device.
2. Select suitable isolator which matches the field device according to its power polarity, signal type and transmission mode.
Operation notes
1. Please read the user manual carefully before using. If any question please contact our technical support department.
2. Please do not use this product in hazardous area.
3. The power supply of this product should be 24VDC power source. It is forbidden to use 220VAC power supply.
4. To avoid invalid explosion protection function, or any failure, users disassemble this product is forbidden.
The copyright and authority for the interpretation of the products are reserved by MORNSUN
TAxxxW-xx 2013.04.10-A/2
Page 2 of 4