English
Language : 

TC100PW Datasheet, PDF (1/4 Pages) MORNSUN Science& Technology Ltd. – Programmable Thermocouple isolators
Programmable Thermocouple
FEATURES
●3-port isolation (Signal input, signal output
isolators
and power supply)
●12.5mm slim case
——TCxxxPW
Series
●
●
High
High
accuracy (0.1% F.S.)
linearity (0.1% F.S.)
● Low temperature drift(50PPM/°C)
● Low-power dissipation
● Excellent EMC performance
● miniUSB port communication
● Input / Output range programmable
● High reliability(MTBF>500,000 hours)
PART NUMBER SYSTEM
TCxxxPW
Slim case
Programmable
Serial number
Channel configuration
Thermalcouple signal
Transducer type
GENERAL DESCRIPTION
TCxxxPW series thermocouple isolator which are mainly
applied in industrial automation systems can isolated
convert thermocouple input signal of the industrial field
instruments to the matched analog output signal for the
DCS/PLC, realizing the acquisition and transmission of field
signal.
An independent power supply is needed for the product
and the port of power supply, input and output are isolated
from each other. This series of products contain
combinations of 1 input 1 output , 1 input 2 output, 2 input 2
output and so on. The thickness of 12.5mm meet the need
for high density field installation.
SELECTION GUIDE
Output type
1 input 1 output
2 input 2 output
1 input 2 output
Current output
TC100PW
TC200PW
TC600PW
Voltage output
TC140PW
TC240PW
TC640PW
Input signal:
Input signal
Range
The minimum range
R
-40~+1700℃
600℃
S
-40~+1700℃
600℃
K
-150~+1370℃
120℃
J
-80~+900℃
100℃
T
-160~+390℃
100℃
B
320~+1820℃
780℃
E
-80~+700℃
500℃
mV
-60~+60mV
10mV
Output signal:
Output type
Output signal
Current output
4~20mA / 0~20mA ( programmable)
Voltage output
0~5V / 0~10V / 1~5V / 2~10V ( programmable)
Note:1. Customers need to choose the type of the input signal, output signal and range. We could also offer customer design for special input and output.
2. You can get the USB Adapter T-01 for the isolator from Mornsun free of charge if you need.
ELECTRICAL CHARACTERISTICS
Input voltage
Power input
Power dissipation
Power protection
Input signal
Field Area
Cold junction compensation
18~30VDC(Typical values 24VDC)
1 input 1output ≤0.9W 1 input 2 output, 2 input 2 output ≤1.2W
Reverse polarity protection, over-voltage protection
See selection guide
Compensation range:-25~+75℃(Error is less than 1 ° C per 20 ℃)
Method of compensation: Internal compensation
The copyright and authority for the interpretation of the products are reserved by MORNSUN
TCxxxPW
2013.06.07-A/1
Page 1 of 4