SW20XX-EX Isolating Switching Barrier
FEATURES
● Fitted devices: 1. NAMUR Sensors;
2. Mechanical Joints.
● Phase-angel and inverse control setting;
● Open circuit detection setting
● Respective Isolation(2,500VDC between
Input/Output/Power source);
● Operation Temperature:-20℃-+60℃
● Reliable Performance (MTBF>1,000,000 Hours).
APPLICATIONS
This Isolation Switching Barrier can detect
switch or approach switch’s status in locations
where hazardous exists; isolate, transmit and
output it to safe area. Input and output can be set
to inverse control. Approach switch open circuit
detection function. Isolation between Input/
Output/Power source.
MODEL SELECTION
SW XXXX-EX
Explos io n protection certification mark
Channe l number
Additional function
Signal o utput mode ( s afe area)
Signal o utput mode ( hazardous a rea)
Detectin g signal type
MORNSUN Guangzhou Science & Technology co., Ltd.
Address: 2/F, Bldg 6, Huangzhou Industrial Park,
Chebei Rd, Tianhe, Guangzhou, China 510660
Tel: 86-20-38601850 39601530 38601679
Fax: 86-20-38601272
http://www.mornsun-power.com
PRODUCT PROGRAM
Input(Power)
Part number
Voltage(VDC)
Typ Range
SW 2001-EX
24
SW 2002-EX
18-36
Output(Hazardous end)
Voltage
Typ
Short Cricuit
Current
8 VDC
< 8 mA
Output
(Safe end)
Relay output
Relay output
Channel
numbers
1
2
ELECTRICAL CHARACTERISTICS
Common
parameter
Operation voltage
Power consumption
Power indicating
Input Signal
Hazardous
Area
Output Voltage
Short circuit current
Input switching frequency
threshold
Safe Area
Output signal
Response time
driving capability
Load type
18-36VDC
About 2.0W (with relay output OFF)
LED light (green) ON when operating
Switch status of NUMAR sensor,
mechanical joint etc
8V(Open status)
<8mA
<10Hz
Typ:1.55mA (hysteresis:0.2mA)
Relay output(1” ON” joint)
<20ms
250VAC / 3A or 30VDC / 3A
Resistive load
TRANSMISSION CHARACTERISTICS
Under phase-angel control
(K1 “OFF”)
Input loop current > 2.1mA, relay output close, channel
indicator light (yellow) ON.
Input loop current < 1.2mA, relay output open, channel
indicator light (yellow) OFF.
Under inverse control
(K1”ON”)
Input loop current > 2.1mA, relay output close, channel
indicator light (yellow) OFF.
Input loop current < 1.2mA, relay output open, channel
indicator light (yellow) ON.
Open detection function
Function when K3 is OFF
When connected with NAMUR Input loop current < 0.05mA, open circuit alarm, channel
sensor
red indicator light ON.
When connected with common To achieve open circuit detection function, a 10KΩ resistor
contact joint switch
must be connected to the switch in parallel.
ISOLATION CHARACTERISTICS
Electrical isolation
Isolation between each part (Signal input end/Signal output end/Power
source end)
Isolation strength 2.5KVDC (test for 1minute, humidity < 70%)
Surge Resist
5KV 1.2/50us (Based on IEC255-4)
EMC
EN61326
MORNSUN reserves the copyright Specifications subject to change without notice.