HDR-100 Datasheet, PDF (2/4 Pages) Mean Well Enterprises Co., Ltd. – 85 ~ 100W Ultra Slim Step Shape DIN Rail
85 ~ 100W Ultra Slim Step Shape DIN Rail
HDR-100 series
SPECIFICATION
MODEL
HDR-100-12 HDR-100-12N HDR-100-15 HDR-100-15N HDR-100-24 HDR-100-24N HDR-100-48 HDR-100-48N
DC VOLTAGE
12V
15V
24V
48V
RATED CURRENT
7.1A
7.5A
6.13A
6.5A
3.83A
4.2A
1.92A
2.1A
CURRENT RANGE
RATED POWER
0 ~ 7.1A
85.2W
0 ~ 7.5A
90W
0 ~ 6.13A
92W
0 ~ 6.5A
97.5W
0 ~ 3.83A
92W
0 ~ 4.2A
100.8W
0 ~1.92A
92.2W
0 ~ 2.1A
100.8W
RIPPLE & NOISE (max.) Note.2 120mVp-p
120mVp-p
150mVp-p
240mVp-p
OUTPUT
VOLTAGE ADJ. Pass LPS
RANGE
Non LPS
VOLTAGE TOLERANCE Note.3
LINE REGULATION
12 ~ 13V
12~ 13.8V
2.0%
1.0%
15 ~ 17V
13.5 ~ 18V
1.0%
1.0%
24 ~ 25.5V
21.6 ~ 29V
1.0%
1.0%
48 ~ 48.7V
43.2 ~ 55.2V
1.0%
1.0%
LOAD REGULATION
1.0%
1.0%
1.0%
1.0%
SETUP, RISE TIME
500ms, 60ms/230VAC 500ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)
30ms/230VAC 12ms/115VAC at full load
VOLTAGE RANGE
85 ~ 264VAC (277VAC operational ) 120 ~ 370VDC (390VDC operational )
FREQUENCY RANGE
47 ~ 63Hz
INPUT EFFICIENCY (Typ.)
88%
89%
90%
90%
AC CURRENT (Typ.)
3A/115VAC 1.6A/230VAC
INRUSH CURRENT (Typ.)
OVERLOAD
PROTECTION
Note.4
OVER VOLTAGE
COLD START 35A/115VAC 70A/230VAC
HDR-100 : 102 ~ 110% rated output power;HDR-100-xxN : 105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
14.2 ~ 16.2V
18.8 ~ 22.5V
30 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
56.5 ~ 64.8V
WORKING TEMP.
-30 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT
0.03%/ (0 ~ 50 ) RH non-condensing
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
OPERATING ALTITUDE 2000 meters
SAFETY STANDARDS
UL60950-1, UL508, TUV EN61558-2-16, IEC60950-1 approved; Design refer to EN50178,TUV EN60950-1
WITHSTAND VOLTAGE
I/P-O/P:3KVAC
ISOLATION RESISTANCE I/P-O/P:100M Ohms / 500VDC / 25 / 70% RH
Parameter
Standard
Test Level / Note
Conducted
EN55032(CISPR32)
Class B
EMC EMISSION
Radiated
EN55032(CISPR32)
Class B
SAFETY &
EMC
(Note 6)
Harmonic Current (Note 5)
EN61000-3-2
Voltage Flicker
EN61000-3-3
EN55024, EN61000-6-2, EN61204-3
Parameter
Standard
Class A
-------
Test Level /Note
ESD
EN61000-4-2
Level 3, 8KV air; Level 2, 4KV contact, criteria A
Radiated Susceptibility
EN61000-4-3
Level 3, criteria A
EMC IMMUNITY
EFT/Burest
Surge
EN61000-4-4
EN61000-4-5
Level 3, criteria A
Level 4,2KV/L-N, criteria A
Conducted
EN61000-4-6
Level 3, criteria A
Magnetic Field
EN61000-4-8
Level 4, criteria A
MTBF
Voltage Dips and interruptions EN61000-4-11
856.5K hrs min. MIL-HDBK-217F (25 )
>95% dip 0.5 periods, 30% dip 25 periods,
>95% interruptions 250 periods
OTHERS DIMENSION
70*90*54.5mm (W*H*D)
PACKING
0.27Kg; 48pcs/14Kg/1.10CUFT
℃
μμ

NOTE






File Name:HDR-100-SPEC 2017-06-22