English
Language : 

SDR-240_11 Datasheet, PDF (1/3 Pages) Mean Well Enterprises Co., Ltd. – 240W Single Output Industrial DIN RAIL with PFC Function
240W Single Output Industrial DIN RAIL with PFC Function
SDR-240 series
Features :
High efficiency 94% and low power dissipation
150% peak load capability
Built-in active PFC function, PF>0.93
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
Built-in DC OK relay contact
100% full load burn-in test
3 years warranty
SPECIFICATION
SEM PQ
I F47
GL
MODEL
SDR-240-24
SDR-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
10A
5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
RATED POWER
240W
240W
PEAK CURRENT
15A
7.5A
PEAK POWER Note.6
360W (3sec.)
OUTPUT RIPPLE & NOISE (max.) Note.2 100mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
24 ~ 28V
48 ~ 55V
VOLTAGE TOLERANCE Note.3 1.0%
1.0%
LINE REGULATION
0.5%
0.5%
LOAD REGULATION
1.0%
1.0%
SETUP, RISE TIME
1500ms, 60ms/230VAC 3000ms, 60ms/115VAC at full load
HOLD UP TIME (Typ.)
20ms/230VAC 20ms/115VAC at full load
VOLTAGE RANGE
88 ~ 264VAC 124 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.93/230VAC 0.99/115VAC at full load
INPUT
EFFICIENCY (Typ.) Note.8 94%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
2.6A/115VAC
33A/115VAC
1.3A/230VAC
65A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
PROTECTION OVER VOLTAGE
29 ~ 33V
Protection type : Shut down o/p voltage with auto-recovery
56 ~ 65V
OVER TEMPERATURE
95 5 (TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
WORKING TEMP.
Note.5 -25 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 95% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
VIBRATION
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY &
EMC
(Note 4)
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC O/P-DC OK:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
SEMI F47, GL approved
MTBF
169.3Khrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
63*125.2*113.5mm (W*H*D)
NOTE
PACKING
1.03Kg; 12pcs/13.4Kg/1.06CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
8. After 30 minutes of burn-in.
File Name:SDR-240-SPEC 2011-08-23