English
Language : 

RSP-3000 Datasheet, PDF (1/5 Pages) Mean Well Enterprises Co., Ltd. – 3000W Single Output Power Supply
3000W Single Output Power Supply
RSP-3000 series
SPECIFICATION
Features :
AC input active surge current limiting
High efficiency up to 90%
Built-in active PFC function,PF>0.95
Protections: Short circuit / Overload / Over voltage / Over temperature
/ Fan Alarm
Forced air cooling by built-in DC with fan speed control function
Output voltage can be trimmed between 20~110% of the rated output voltage
High power density 15.6W/inch3
Current sharing up to 2 units
Alarm signal output
Built-in 12V/0.1A auxiliary output for remote control
Built-in remote ON-OFF control
Built-in remote sense function
3 years warranty
MODEL
RSP-3000-12
RSP-3000-24
RSP-3000-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
200A
125A
62.5A
CURRENT RANGE
0 ~ 200A
0 ~ 125A
0 ~ 62.5A
RATED POWER
2400W
3000W
3000W
RIPPLE & NOISE (max.) Note.2 150mVp-p
150mVp-p
200mVp-p
OUTPUT VOLTAGE ADJ. RANGE
10.8 ~ 13.2V
22 ~ 28V
43 ~ 56V
VOLTAGE TOLERANCE Note.3 1.0%
1.0%
1.0%
LINE REGULATION
0.5%
0.5%
0.5%
LOAD REGULATION
0.5%
0.5%
0.5%
SETUP, RISE TIME
1000ms, 80ms at full load
HOLD UP TIME (Typ.)
10ms at full load
VOLTAGE RANGE
180 ~ 264VAC 254 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.95/230VAC at full load
INPUT EFFICIENCY (Typ.)
86%
89%
90%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
20A/180VAC
60A/230VAC
16A/230VAC
LEAKAGE CURRENT
<2.0mA / 240VAC
OVERLOAD
100 ~ 110% rated output power
Note.5 Protection type : Constant current limiting unit will shut down o/p voltage after 5sec. Re-power on to recover
PROTECTION OVER VOLTAGE
13.8 ~ 16.8V
28.8 ~ 33.6V
Protection type : Shut down o/p voltage, re-power on to recover
57.6 ~ 67.2V
90 5 (12V), 110 5 (24V), 105 5 (48V) (TSW1: detect on heatsink of power transistor)
OVER TEMPERATURE
90 5 (12V), 85 5 (24V), 75 5 (48V) (TSW2 : detect on heatsink of o/p diode)
AUXILIARY POWER(AUX)
REMOTE ON/OFF CONTROL
FUNCTION ALARM SIGNAL OUTPUT
OUTPUT VOLTAGE TRIM
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
12V@0.1A(Only for Remote ON/OFF control)
Please see the Function Manual
Please see the Function Manual
2.4 ~ 13.2V
4.8 ~ 28V
9.6 ~ 56V
CURRENT SHARING
Please see the Function Manual
WORKING TEMP.
WORKING HUMIDITY
-20 ~ +70 (Refer to output load derating curve)
20~90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
VIBRATION
0.05%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22)
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
MTBF
104.5K hrs min. MIL-HDBK-217F (25 )
OTHERS
NOTE
DIMENSION
278*177.8*63.5mm (L*W*H)
PACKING
4Kg; 4pcs/16Kg/1.89CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. The disposition of output load line each must out of bounds to PSU with ten CM.
File Name:RSP-3000-SPEC 2008-12-09