English
Language : 

RSP-2000_1112 Datasheet, PDF (1/5 Pages) Mean Well Enterprises Co., Ltd. – 2000W Single Output Power Supply
2000W Single Output Power Supply
RSP-2000 series
Features :
Universal AC input / Full range
Built-in 5V/0.3A, 12V/0.8A auxiliary power
Built-in active PFC function, PF>0.97
Protections: Short circuit / Overload / Over voltage / Over temperature
Forced air cooling by built-in DC fan with fan speed control
Output voltage can be trimmed between 40~115% of the rated output voltage
High Power density 21.4W/inch3
1U low profile 41mm
Active current sharing up to 8000W(3+1)
Built-in remote ON-OFF control
Built-in remote sense function
DC OK signal, OTP alarm signal
3 years warranty
SPECIFICATION
MODEL
RSP-2000-12
RSP-2000-24
RSP-2000-48
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
12V
100A
0 ~ 100A
1200W
24V
80A
0 ~ 80A
1920W
48V
42A
0 ~ 42A
2016W
OUTPUT
RIPPLE & NOISE (max.) Note.2 150mVp-p
VOLTAGE ADJ. RANGE
10.5 ~ 14V
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
1.0%
LOAD REGULATION
1.0%
200mVp-p
21 ~ 28V
1.0%
0.5%
0.5%
300mVp-p
42 ~ 56V
1.0%
0.5%
0.5%
SETUP, RISE TIME
1500ms, 60ms/230VAC at full load
HOLD UP TIME (Typ.)
16ms/230VAC at 75% load 10ms/230VAC at full load
VOLTAGE RANGE
Note.5 90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
127 ~ 370VDC
POWER FACTOR (Typ.)
0.97/230VAC at full load
INPUT
EFFICIENCY (Typ.)
87%
AC CURRENT (Typ.) Note.5 13A/115VAC 7A/230VAC
INRUSH CURRENT (Typ.) COLD START 50A
90.5%
16A/115VAC
10A/230VAC
92%
16A/115VAC
10A/230VAC
LEAKAGE CURRENT
<2mA / 240VAC
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
105 ~ 125% rated output power
Protection type : Constant current limiting, unit will shut down o/p voltage after 5 sec. re-power on to recover
14.7 ~ 17.5V
29.5 ~ 35V
57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
80 5 (TSW1) detect on heatsink of power bridge 75 5 (TSW2) detect on heatsink of o/p diode
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
AUXILIARY POWER
REMOTE ON/OFF CONTROL
FUNCTION REMOTE SENSE
DC OK SIGNAL
OUTPUT VOLTAGE TRIM
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
5V @ 0.3A, 12V @ 0.8A
By electrical signal or dry contact Power ON:open Power OFF:short, refer to function manual
Compensate voltage drop on the load wiring up to 0.5V, refer to function manual
The isolated TTL signal out, refer to function manual
Adjustment of output voltage, possible between 40 ~ 115% of rated output, refer to function manual
-35 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE
(Note 4) EMC EMISSION
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Conduction Class B, Radiation Class A ; EN61000-3-2,-3
EMC IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
46.3Khrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
PACKING
295*127*41mm (L*W*H)
1.95Kg; 6pcs/12.7Kg/1.15CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Under parallel operation ripple of the output voltage may be higher than the SPEC at light load condition. It will go back to normal ripple level once the
output load is more than 5%.
File Name:RSP-2000-SPEC 2011-12-27