English
Language : 

RS-35_10 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 35W Single Output Switching Power Supply
35W Single Output Switching Power Supply
RS-35 series
Features :
Universal AC input / Full range
Protections: Short circuit / Over load / Over voltage
Cooling by free air convection
LED indicator for power on
100% full load burn-in test
No load power consumption<0.5W
All using 105 long life electrolytic capacitors
Withstand 300VAC surge input for 5 second
High operating temperature up to 70
Withstand 5G vibration test
High efficiency, long life and high reliability
3 years warranty
SPECIFICATION
MODEL
RS-35-3.3
RS-35-5
RS-35-12
RS-35-15
RS-35-24
RS-35-48
OUTPUT
INPUT
DC VOLTAGE
3.3V
5V
12V
15V
24V
RATED CURRENT
7A
7A
3A
2.4A
1.5A
CURRENT RANGE
0 ~ 7A
0 ~ 7A
0 ~ 3A
0 ~ 2.4A
0 ~ 1.5A
RATED POWER
23.1W
35W
36W
36W
36W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
120mVp-p
120mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
2.9V ~ 3.6V
4.5 ~ 5.5V
10.8 ~ 13.2V
13.5 ~ 16.5V
22 ~ 27.6V
VOLTAGE TOLERANCE Note.3 3.0%
2.0%
1.0%
1.0%
1.0%
LINE REGULATION Note.4 0.5%
0.5%
0.5%
0.5%
0.5%
LOAD REGULATION Note.5 2.0%
1.0%
0.5%
0.5%
0.5%
SETUP, RISE TIME
500ms, 50ms/230VAC 1200ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)
80ms/230VAC 15ms/115VAC at full load
VOLTAGE RANGE
88 ~ 264VAC 125 ~ 373VDC (Withstand 300VAC surge for 5sec. Without damage)
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY(Typ.)
76.5%
80.5%
84.5%
86%
88%
AC CURRENT (Typ.)
0.8A/115VAC 0.55A/230VAC
INRUSH CURRENT (Typ.) COLD START 36A/230VAC
48V
0.8A
0 ~ 0.8A
38.4W
200mVp-p
42 ~ 54V
1.0%
0.5%
0.5%
88.5%
LEAKAGE CURRENT
<2mA / 240VAC
OVERLOAD
PROTECTION
OVER VOLTAGE
110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
3.8 ~ 4.45V
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
27.6 ~ 32.4V
55.2 ~ 64.8V
WORKING TEMP.
-25 ~ +70 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0 ~ 50 )
VIBRATION
10 ~ 500Hz, 5G 10min./1cycle, period for 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 6)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
249Khrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
99*82*36mm (L*W*H)
PACKING
0.3Kg; 45pcs/14Kg/0.83CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:RS-35-SPEC 2010-10-18