RS-100_11 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 100W Single Output Switching Power Supply
100W Single Output Switching Power Supply
RS-100 series
Features :
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
LED indicator for power on
100% full load burn-in test
All using 105 long life electrolytic capacitors
Withstand 300VAC surge input for 5 second
High operating temperature up to 70
Withstand 5G vibration test
High efficiency, long life and high reliability
3 years warranty
SPECIFICATION
MODEL
RS-100-3.3
RS-100-5
RS-100-12
RS-100-15
RS-100-24
RS-100-48
DC VOLTAGE
3.3V
5V
12V
15V
24V
48V
RATED CURRENT
20A
16A
8.5A
7A
4.5A
2.3A
CURRENT RANGE
0 ~ 20A
0 ~ 16A
0 ~ 8.5A
0 ~ 7A
0 ~ 4.5A
0 ~ 2.3A
RATED POWER
66W
80W
102W
105W
108W
110.4W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
120mVp-p
120mVp-p
120mVp-p
200mVp-p
OUTPUT
VOLTAGE ADJ. RANGE
3.2V ~ 3.5V
4.75 ~ 5.5V
11.4 ~ 13.2V
VOLTAGE TOLERANCE Note.3 3.0%
2.0%
1.0%
LINE REGULATION Note.4 0.5%
0.5%
0.5%
LOAD REGULATION Note.5 2.0%
1.0%
0.5%
SETUP, RISE TIME
500ms, 20ms/230VAC 1200ms, 30ms/115VAC at full load
14.25 ~ 16.5V
1.0%
0.5%
0.5%
22.8 ~ 26.4V
1.0%
0.5%
0.5%
45.6 ~ 52.8V
1.0%
0.5%
0.5%
HOLD UP TIME (Typ.)
100ms/230VAC 18ms/115VAC at full load
VOLTAGE RANGE
88 ~ 264VAC 125 ~ 373VDC (Withstand 300VAC surge for 5sec. Without damage)
FREQUENCY RANGE
47 ~ 63Hz
INPUT
EFFICIENCY (Typ.)
74%
77%
81%
82%
84%
84%
AC CURRENT (Typ.)
2.5A/115VAC 1.5A/230VAC
INRUSH CURRENT (Typ.) COLD START 40A/230VAC
LEAKAGE CURRENT
<2mA / 240VAC
OVERLOAD
PROTECTION
OVER VOLTAGE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
110 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
3.8 ~ 4.45V
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
-25 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50 )
27.6 ~ 32.4V
55.2 ~ 64.8V
VIBRATION
10 ~ 500Hz, 5G 10min./1cycle, period for 60min. each along X, Y, Z axes
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE
(Note 6) EMC EMISSION
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
OTHERS
NOTE
MTBF
260.8Khrs min. MIL-HDBK-217F (25 )
DIMENSION
159*97*38mm (L*W*H)
PACKING
0.6Kg; 24pcs/15.4Kg/0.7CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. Line regulation is measured from low line to high line at rated load.
5. Load regulation is measured from 0% to 100% rated load.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
7. Length of set up time is measured at cold first start. Turning ON/OFF the power supply very quickly may lead to increase of the set up time.
File Name:RS-100-SPEC 2011-08-19