English
Language : 

RCP-MU_11 Datasheet, PDF (1/3 Pages) Mean Well Enterprises Co., Ltd. – Power Control and Monitor System
Power Control and Monitor System
RCP-MU
Features :
1U low profile
19-inch rack mounting
Control and monitor up to 3 RCP-1000 units
Suitable for all kinds of RCP output (12V,24V,48V)
Digital meters for output voltage, output current, and internal temperature
on front panel
Potential meter for adjusting output voltage of RCP-1000 unit on front panel
Relay contacts and LED indicators for AC fail, DC fail, and over temperature
warning
Removable fixing accessory
3 years warranty
Description : RCP-MU is the monitoring and control unit used for the RCP-1000 series rack power. It can decode the I2C signal sent by
RCP series and display through digital meters or relay contact signals. RCP-MU can also turn ON/OFF or trim the output
voltage of RCP-1000 remotely that make the basic control more easily.
SPECIFICATION
MODEL
RCP-MU
VOLTAGE RANGE
90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
INPUT
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
0.35A/115VAC 0.2A/230VAC
30A/115VAC 50A/230VAC
MONITORING INPUTS
I2C signal ( AC OK, DC OK, and over temperature alarm signals for each RCP-1000 unit ), output voltage of the RCP-1U rack
DIGITAL METER
Note.2 Display the DC output voltage, current, and internal temperature of each RCP-1000 unit
CONTROL OUTPUT
OUTPUT
RELAY CONTACT
Remote ON/OFF and output voltage trimming for each RCP-1000 unit
Alarm for AC Fail, DC Fail, and Over Temperature ; rating : 30VDC, 1A
LED INDICATOR
AC Fail, DC Fail, Over Temperature
REMOTE ON/OFF CONTROL
FUNCTION
VOLTAGE TRIM
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT
STORAGE TEMP., HUMIDITY
The controlled RCP-1000 unit can be turned ON/OFF on the front panel for RCP-MU
Output voltage of the controlled RCP-1000 unit and be trimmed by 10% on the front panel of RCP-MU
-20 ~ +60
20~90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
VIBRATION
SAFETY STANDARDS
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
Design refer to UL60950-1, TUV EN60950-1
SAFETY & WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11
OTHERS
NOTE
DIMENSION
440*68*44mm (L*W*H)
PACKING
1.15Kg; 6pcs/8Kg/1.27CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Resolution and tolerance of the values shown on the digital meter depends on the controlled RCP series.
File Name:RCP-MU-SPEC 2011-08-19