English
Language : 

PSP-1000 Datasheet, PDF (1/2 Pages) Total Power International – 1000W Single Output with PFC Function
1000W Single Output with PFC Function
PSP-1000 series
Features :
Universal AC input / Full range
AC input active surge current limiting
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage / Over temperature
Built-in constant current limiting circuit
Current sharing up to 2 units or 2000W
Built-in remote ON-OFF control
Built-in remote sense function
Built-in active current sharing and parallel function
3 years warranty
SPECIFICATION
MODEL
PSP-1000-5 PSP-1000-12 PSP-1000-13.5 PSP-1000-15 PSP-1000-24 PSP-1000-27 PSP-1000-48
OUTPUT
INPUT
DC VOLTAGE
5V
12V
13.5V
15V
RATED CURRENT
145A
75A
67A
60A
CURRENT RANGE
0 ~ 145A
0 ~ 75A
0 ~ 67A
0 ~ 60A
RATED POWER
725W
900W
904.5W
900W
PEAK LOAD
Note.4 800W
1000W
1000W
1000W
RIPPLE & NOISE (max.) Note.2 100mVp-p
150mVp-p
150mVp-p
150mVp-p
VOLTAGE ADJ. RANGE
4.75 ~ 5.5V
10 ~ 13.2V
12 ~ 15V
13.5 ~ 18V
VOLTAGE TOLERANCE Note.3 6.0%
3.0%
2.0%
2.0%
LINE REGULATION
0.5%
0.3%
0.3%
0.3%
LOAD REGULATION
2.0%
0.5%
0.5%
0.5%
SETUP, RISE TIME
1500ms, 50ms/230VAC 1500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)
24ms/230VAC 24ms/115VAC at full load
VOLTAGE RANGE Note.6 90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.96/230VAC 0.96/115VAC at full load
EFFICIENCY (Typ.)
77%
84%
84%
84%
AC CURRENT (Typ.)
11.2A/115AVC 5.6A/230VAC
INRUSH CURRENT (Typ.) 32A/115VAC 63A/230VAC
24V
37.6A
0 ~ 37.6A
902.4W
1000W
150mVp-p
20 ~ 26.4V
1.0%
0.2%
0.5%
85%
27V
33.6A
0 ~ 33.6A
907.2W
1000W
150mVp-p
24 ~ 30V
1.0%
0.2%
0.5%
86%
48V
19A
0 ~ 19A
912W
1000W
200mVp-p
41 ~ 56V
1.0%
0.2%
0.5%
86%
LEAKAGE CURRENT
<2mA / 240VAC
OVERLOAD
115 ~ 140% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
PROTECTION OVER VOLTAGE
5.75 ~ 6.75V 13.8 ~ 16.2V 15.5 ~ 18.2V 18 ~ 21V
Protection type : Shut down o/p voltage, re-power on to recover
27.6 ~ 32.4V 31 ~ 36.5V
57.6 ~ 67.2V
OVER TEMPERATURE
95 (TSW1) detect on the heatsink of PFC MOSFET 90 (TSW2) detect the winding of output choke
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION REMOTE CONTROL
RC+/RC-: 0 ~ 0.8V=power on ; 4 ~ 10V=power off sink current <20mA
WORKING TEMP.
-10 ~ +60 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0 ~ 50
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 5)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
MTBF
59.6K hrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
278*129*127mm (L*W*H)
NOTE
PACKING
5.2Kg; 3pcs/16.3Kg/1.42CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. 10% Duty cycle maximum within every 30 seconds(max.). Average output power should not exceed the rated power.
5. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
6. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:PSP-1000-SPEC 2008-06-30