English
Language : 

PSC-60 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 60W Single Output with Battery Charger(UPS Function)
P S C - 6 0 60W Single Output with Battery Charger(UPS Function)
series
Features :
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
Battery low protections / Battery polarity protection by fuse
Alarm signal for AC OK and Bat. low
Cooling by free air convection
100% full load burn-in test
2 years warranty
SPECIFICATION
MODEL
PSC-60A
PSC-60B
OUTPUT NUMBER
CH1
CH2
CH1
CH2
DC VOLTAGE
13.8V
13.8V
27.6V
27.6V
RATED CURRENT
2.8A
1.5A
1.4A
0.75A
CURRENT RANGE
0 ~ 4.3A
--------
0 ~ 2.15A
--------
OUTPUT
RATED POWER
59.34W
RIPPLE & NOISE (max.) Note.2 120mVp-p
VOLTAGE ADJ. RANGE
CH1: 12 ~ 15V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
--------
--------
--------
59.34W
240mVp-p
CH1: 24 ~ 29V
1.0%
0.5%
--------
--------
--------
LOAD REGULATION
0.5%
--------
0.5%
--------
SETUP, RISE TIME
800ms, 50ms/230VAC 1600ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
50ms/230VAC 10ms/115VAC at full load
90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
84%
84%
INPUT
AC CURRENT (Typ.)
1.6A/115VAC 1A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC 60A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
PROTECTION
OVER VOLTAGE
CH1:14.49 ~ 18.63V
CH1:28.98 ~ 37.26V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
BATTERY CUT OFF
10.5 0.5V
21 1V
AC OK
TTL open collector output, ON : AC OK ; OFF : AC Fail ; Ice : max. 30mA@ 50VDC
FUNCTION
BATTERY LOW
TTL open collector output, ON : Battery Low ; OFF : Battery OK ; Ice : max. 30mA@ 50VDC
Battery low voltage < 11V
Battery low voltage < 22V
WORKING TEMP.
-20 ~ +70 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0~50 ) on CH1 output
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
MTBF
589.7K hrs min. MIL-HDBK-217F (25 )
OTHERS
NOTE
DIMENSION
101.6*50.8*29mm (L*W*H)
PACKING
0.13Kg; 96pcs/13.5Kg/0.89CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. Heat Sink HS1,HS2 can not be shorted.
7. Heat Sink HS1 must have safety isolation distance with system case.
File Name:PSC-60-SPEC 2008-11-04