PSC-100 Datasheet, PDF (1/3 Pages) Mean Well Enterprises Co., Ltd. – 100W Single Output with Battery Charger(UPS Function)
P S C - 1 0 0 100W Single Output with Battery Charger(UPS Function)
series
Features :
Universal AC input / Full range
5"x3" compact size
Optional L-Bracket and cover (PSC-100x-C, x=A,B)
Protections: Short circuit / Overload / Over voltage
Battery low protection / Battery polarity protection by fuse
Relay contact signal output for AC OK and Battery Low
Cooling by free air convection
100% full load burn-in test
2 years warranty
SPECIFICATION
MODEL
PSC-100A
PSC-100B
OUTPUT
INPUT
OUTPUT NUMBER
CH1
CH2
CH1
DC VOLTAGE
13.8V
13.8V
27.6V
RATED CURRENT
4.75A
2.5A
2.4A
CURRENT RANGE
0 ~ 7A
--------
0 ~ 3.5A
RATED POWER
100W
100.74W
RIPPLE & NOISE (max.) Note.2 100mVp-p
--------
100mVp-p
VOLTAGE ADJ. RANGE
CH1: 12 ~ 15V
CH1: 24 ~ 29V
VOLTAGE TOLERANCE Note.3 1.0%
--------
1.0%
LINE REGULATION
0.5%
--------
0.5%
LOAD REGULATION
0.5%
--------
0.5%
SETUP, RISE TIME Note.5 2400ms, 30ms/230VAC 2400ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
40ms/230VAC 16ms/115VAC at full load
VOLTAGE RANGE
90 ~ 264VAC 127 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
86%
88%
AC CURRENT (Typ.)
2A/115VAC 1.2A/230VAC
INRUSH CURRENT (Typ.) COLD START 35A/115VAC 70A/230VAC
CH2
27.6V
1.25A
--------
--------
--------
--------
--------
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
PROTECTION
OVER VOLTAGE
CH1:14.49 ~ 18.63V
CH1:28.98 ~ 37.26V
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY CUT OFF
10 0.5V
20 1V
AC OK
ALARM
FUNCTION BATTERY LOW
Note.6 Relay contact output, ON : AC OK ; OFF : AC Fail ; Max. rating : 30V / 1A
Relay contact output, OFF : Battery OK ; ON : Battery Low ; Max. rating : 30V / 1A
Battery low voltage : < 11V
Battery low voltage : < 22V
WORKING TEMP.
-20 ~ +70 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0~50 ) on CH1 output
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
MTBF
417.6K hrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
PCB:127*76.2*31mm (L*W*H) ; with optional CASE:130*85*37mm (L*W*H)
PACKING
PCB:0.23Kg; 63pcs/15.5Kg/1.35CUFT ; with optional CASE:0.44Kg;32pcs/15Kg/0.64CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
6. Please refer to suggest application (2) (4) in page 3.
7. Heat sink HS2,HS3 can not be shorted.
8. Heat sink HS2,HS3 must have safety isolation distance from system case.
File Name:PSC-100-SPEC 2011-03-03