MSP-200 Datasheet, PDF (1/3 Pages) Mean Well Enterprises Co., Ltd. – 200W Single Output Medical Type
200W Single Output Medical Type
MSP-200 series
¡½ Features :
¡EUniversal AC input / Full range
¡EBuilt-in active PFC function, PF>0.95
¡EHigh efficiency up to 89%
¡EWithstand 300VAC surge input for 5 seconds
¡EProtections: Short circuit / Overload / Over voltage / Over temperature
¡ECooling by free air convection
¡EBuilt-in constant current limiting circuit
¡E1U low profile 38mm
¡EBuilt-in remote ON-OFF control
¡EStandby 5V@0.3A
¡EBuilt-in remote sense function
¡ENo load power consumption<0.5W (Note.6)
¡E5 years warranty
SPECIFICATION
MODEL
MSP-200-3.3 MSP-200-5 MSP-200-7.5 MSP-200-12 MSP-200-15 MSP-200-24 MSP-200-36 MSP-200-48
OUTPUT
DC VOLTAGE
3.3V
5V
7.5V
12V
15V
RATED CURRENT
40A
35A
26.7A
16.7A
13.4A
CURRENT RANGE
0 ~ 40A
0 ~ 35A
0 ~ 26.7A
0 ~ 16.7A
0 ~ 13.4A
RATED POWER
132W
175W
200.3W
200.4W
201W
RIPPLE & NOISE (max.) Note.2 80mVp-p
90mVp-p
100mVp-p 120mVp-p 150mVp-p
VOLTAGE ADJ. RANGE
2.8 ~ 3.8V
¡Ó VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
¡Ó0.5%
LOAD REGULATION
¡Ó1.5%
4.3 ~ 5.8V
¡Ó2.0%
¡Ó0.5%
¡Ó1.0%
6.8 ~ 9V
¡Ó2.0%
¡Ó0.5%
¡Ó1.0%
10.2 ~ 13.8V
¡Ó1.0%
¡Ó0.3%
¡Ó0.5%
13.5 ~ 18V
¡Ó1.0%
¡Ó0.3%
¡Ó0.5%
SETUP, RISE TIME
1000ms, 50ms/230VAC 2500ms, 50ms/115VAC at full load
HOLD UP TIME (Typ.)
16ms/230VAC 16ms/115VAC at full load
24V
8.4A
0 ~ 8.4A
201.6W
150mVp-p
21.6 ~ 28.8V
¡Ó1.0%
¡Ó0.2%
¡Ó0.5%
36V
5.7A
0 ~ 5.7A
205.2W
250mVp-p
28.8 ~ 39.6V
¡Ó1.0%
¡Ó0.2%
¡Ó0.5%
48V
4.3A
0 ~ 4.3A
206.4W
250mVp-p
40.8 ~ 55.2V
¡Ó1.0%
¡Ó0.2%
¡Ó0.5%
VOLTAGE RANGE Note.5 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
PF>0.95/230VAC PF>0.99/115VAC at full load
INPUT EFFICIENCY (Typ.)
80%
84%
86%
88%
88%
88%
89%
89%
AC CURRENT (Typ.)
2.2A/115VAC 1.1A/230VAC
INRUSH CURRENT (Typ.) 35A/115VAC 70A/230VAC
£g £g LEAKAGE CURRENT Note.7 Earth leakage current < 300 A/264VAC , Touch leakage current < 100 A/264VAC
OVERLOAD
105 ~ 135% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE
PROTECTION
OVER TEMPERATURE
3.96 ~ 4.62V 6 ~ 7V
9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V
Protection type : Shut down o/p voltage, re-power on to recover
¢J¡Ó ¢J 95 5 (TSW1) detect on heatsink of power transistor
¢J¡Ó ¢J 105 5 (TSW2) detect on main power output choke
30 ~ 34.8V
41.4 ~ 48.6V
FUNCTION
5V STANDBY
REMOTE CONTROL
WORKING TEMP.
¡Ó Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
5VSB : 5V@0.3A ; tolerance 5%, ripple : 50mVp-p(max.)
RC+/RC- : 4 ~10V or open = power on ; 0 ~ 0.8V or short = power off
¢J -40 ~ +70 (Refer to "Derating Curve")
¢J WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
¡Ó0.03%/¢J (0 ~ 50¢J)
VIBRATION
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
ANSI/AAMI ES60601-1, IEC60601-1 approved
SAFETY & WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE
(Note 4) EMC EMISSION
I/P-O/P:4KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
¢J I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011 (CISPR11) Class B, EN61000-3-2,-3
EMC IMMUNITY
MTBF
Compliance to EN61000-4-2,3,4,5,6,8,11, EN60601-1-2
¢J 209.4K hrs min. MIL-HDBK-217F (25 )
57.6 ~ 67.2V
OTHERS
NOTE
DIMENSION
199*98*38mm (L*W*H)
PACKING
0.77Kg; 18pcs/14.9Kg/0.9CUFT
¢J 1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. No load power consumption<0.5W when RC+ & RC- (CN100 pin1,2) 0 ~ 8V or short.
7. Touch current was measured from primary input to DC output.
File Name:MSP-200-SPEC 2012-06-29