MDR-60_11 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 60W Single Output Industrial DIN Rail Power Supply
60W Single Output Industrial DIN Rail Power Supply
MDR-60 series
Features :
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
NEC class 2 / LPS compliant (24V,48V only)
LED indicator for power on
DC OK relay contact
No load power consumption<0.75W
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
MDR-60-5
MDR-60-12
MDR-60-24
MDR-60-48
DC VOLTAGE
5V
12V
24V
48V
RATED CURRENT
10A
5A
2.5A
1.25A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
0 ~ 2.5A
0 ~ 1.25A
RATED POWER
50W
60W
60W
60W
OUTPUT
RIPPLE & NOISE (max.) Note.2 80mVp-p
VOLTAGE ADJ. RANGE
5 ~ 6V
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
1.0%
120mVp-p
12 ~ 15V
1.0%
1.0%
150mVp-p
24 ~ 30V
1.0%
1.0%
200mVp-p
48 ~ 56V
1.0%
1.0%
LOAD REGULATION
1.5%
1.0%
1.0%
1.0%
SETUP, RISE TIME Note.5 500ms, 30ms/230VAC 500ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
50ms/230VAC 20ms/115VAC at full load
VOLTAGE RANGE
85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
78%
86%
88%
87%
INPUT
AC CURRENT (Typ.)
1.8A/115VAC 1A/230VAC
INRUSH CURRENT (Typ.) COLD START 30A/115VAC 60A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
PROTECTION
OVER VOLTAGE
FUNCTION DC OK SIGNAL
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
6.25 ~ 7.25V
15.6 ~ 18V
31.2 ~ 36V
Protection type : Shut down o/p voltage, re-power on to recover
Relay contact rating(max.): 30V/1A resistive
-20 ~ +70 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-40 ~ +85 , 10 ~ 95% RH
57.6 ~ 64.8V
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
EMC
(Note 4)
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
MTBF
OTHERS DIMENSION
PACKING
0.03%/ (0 ~ 50
Component : 10 ~ 500Hz, 2G 10min./1cycle, period for 60min. each along X, Y, Z axes ; Mounting : Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved, NEC class 2 / LPS compliant (24V,48V only)
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
299.2K hrs min. MIL-HDBK-217F (25 )
40*90*100mm (W*H*D)
0.33Kg; 42pcs/14.8Kg/0.82CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
File Name:MDR-60-SPEC 2011-05-24