English
Language : 

MDR-10_11 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 10W Single Output Industrial DIN Rail Power Supply
10W Single Output Industrial DIN Rail Power Supply
MDR-10 series
Features :
Universal AC input/Full range
Protections: Short circuit / Overload / Over voltage
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
NEC class 2 / LPS compliant
Built in DC OK active signal
LED indicator for power on
No load power consumption<0.75W
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
MDR-10-5
MDR-10-12
MDR-10-15
MDR-10-24
DC VOLTAGE
5V
12V
15V
24V
RATED CURRENT
2A
0.84A
0.67A
0.42A
CURRENT RANGE
0 ~ 2A
0 ~ 0.84A
0 ~ 0.67A
0 ~ 0.42A
RATED POWER
10W
10W
10W
10W
OUTPUT
RIPPLE & NOISE (max.) Note.2 80mVp-p
VOLTAGE TOLERANCE Note.3 5.0%
LINE REGULATION
1.0%
120mVp-p
3.0%
1.0%
120mVp-p
3.0%
1.0%
150mVp-p
2.0%
1.0%
LOAD REGULATION
5.0%
3.0%
3.0%
2.0%
SETUP, RISE TIME Note.5 500ms, 30ms/230VAC 1000ms, 30ms/115VAC at full load
HOLD UP TIME (Typ.)
120ms/230VAC 25ms/115VAC at full load
VOLTAGE RANGE
85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
77%
81%
81%
84%
INPUT
AC CURRENT (Typ.)
0.33A/115VAC 0.21A/230VAC
INRUSH CURRENT (Typ.) COLD START 35A/115VAC 70A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
PROTECTION
OVER VOLTAGE
Above 105% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
5.75 ~ 6.75V
13.8 ~ 16.2V
17.25 ~ 20.25V
Protection type : Shut down o/p voltage, re-power on to recover
FUNCTION DC OK ACTIVE SIGNAL (max.) 3.75 ~ 6V / 50mA
9 ~ 13.5V / 40mA
11.5 ~ 16.5V / 40mA
27.6 ~ 32.4V
18 ~ 27V / 20mA
WORKING TEMP.
-20 ~ +70 (Refer to "Derating Curve")
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
SAFETY &
EMC
(Note 4)
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved, NEC class 2 / LPS compliant
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024,EN61000-6-1,EN61204-3, light industry level, criteria A
OTHERS
MTBF
DIMENSION
PACKING
584K hrs min. MIL-HDBK-217F (25 )
22.5*90*100mm (W*H*D)
0.17Kg; 72pcs/13.2Kg/0.91CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time.
File Name:MDR-10-SPEC 2011-05-24