SPECIFICATION
MODEL
HSN-300-4.2A
HSN-300-4.2B
HSN-300-5A
HSN-300-5B
OUTPUT
DC VOLTAGE
4.2V
RATED CURRENT
Note.2 50A
CURRENT RANGE
0 ~ 50A
RATED POWER(convection) 210W
RIPPLE & NOISE (max.) Note.3 150mVp-p
4.2V
60A
0 ~ 60A
252W
150mVp-p
5V
50A
0 ~ 50A
250W
150mVp-p
5V
60A
0 ~ 60A
300W
150mVp-p
VOLTAGE ADJ. RANGE
3.6~4.4V
VOLTAGE TOLERANCE Note.4 ±3.0%
LINE REGULATION
±0.5%
LOAD REGULATION
±2.0%
3.6~4.4V
±3.0%
±0.5%
±2.0%
4.5~5.5V
±3.0%
±0.5%
±2.0%
4.5~5.5V
±3.0%
±0.5%
±2.0%
SETUP, RISE TIME
2500ms, 100ms/230VAC; 2500ms, 100ms/115VAC
HOLD UP TIME (Typ.)
10ms/230VAC; 8ms/115VAC at full load
VOLTAGE RANGE
90~132VAC or 254~373VDC 180~264VAC or 254~373VDC 90~132VAC or 254~373VDC 180~264VAC or 254~373VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
85%
86%
INPUT
AC CURRENT (Typ.)
3.0A/230VAC; 5.0A/115VAC
INRUSH CURRENT (Typ.) Cold start 90A/230VAC
LEAKAGE CURRENT
<1mA
OVERLOAD
SHORT CIRCUIT
PROTECTION
OVER VOLTAGE
A Type:105~170% rated output power B Type:105~140% rated output power
Protection type : Hiccup mode, recovers automatically after fault condition is removed
Protection type : Hiccup mode, recovers automatically after fault condition is removed
4.7 ~ 5.7V
5.7 ~ 7.0V
Protection type : Hiccup mode, recovers automatically after fault condition is removed
OVER TEMPERATURE
WORKING TEMP.
Protection type : Shut down O/P voltage, recovers automatically after temperature goes down
-20 ~ +70℃(Refer to "Derating Curve")
ENVIRONMENT
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
20 ~ 90% RH non-condensing
-40 ~ +85℃, 10 ~ 95% RH
±0.03%/℃ (0 ~ 60℃)
10 ~ 500Hz, 3G 10min./1cycle, 60min. each along X, Y, Z axes
UL60950-1 approved
SAFETY &
EMC
(Note 5)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
EMC IMMUNITY
I/P-O/P:3.0KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC/25℃/ 70%RH
Refer to EN55022 (CISPR22) Class A
Refer to EN61000-4-5; light industry level (surge 4KV), criteria A
OTHERS
MTBF
DIMENSION
PACKING
226.4K hrs min. MIL-HDBK-217F (25℃)
210*81*31mm (L*W*H)
0.67kg; 20pcs/14.4kg/0.91CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
2. Please refer to”static characteristics".
3. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
4. Tolerance : line regulation and load regulation.
5. Derating may be needed under low input voltages. Please check the static characteristics for more details.
6. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:HSN-300-SPEC 2014-12-09