100W Single Output with PFC Function
HRP-100 series
Features :
Universal AC input / Full range
Built-in active PFC function
High efficiency up to 90%
Withstand 300VAC surge input for 5 seconds
Protections: Short circuit / Overload / Over voltage
Protections: Over temperature (optional)
Cooling by free air convection
1U low profile 38mm
Built-in remote ON-OFF control
No load power consumption<0.5W
All using 105 long life electrolytic capacitors
5 years warranty
SPECIFICATION
MODEL
HRP-100-3.3 HRP-100-5 HRP-100-7.5 HRP-100-12 HRP-100-15 HRP-100-24 HRP-100-36 HRP-100-48
OUTPUT
DC VOLTAGE
3.3V
5V
7.5V
12V
15V
RATED CURRENT
20A
17A
13.5A
8.5A
7A
CURRENT RANGE
0 ~ 20A
0 ~ 17A
0 ~ 13.5A
0 ~ 8.5A
0 ~ 7A
RATED POWER
66W
85W
101.3W
102W
105W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
100mVp-p 120mVp-p 150mVp-p
VOLTAGE ADJ. RANGE
3.1 ~ 3.8V 4.75 ~ 5.8V 7.1 ~ 9V
11.4 ~ 13.8V 14.25 ~ 18V
VOLTAGE TOLERANCE Note.3 +2.5,-3.5%
2.5%
2.5%
1.5%
1.5%
LINE REGULATION
0.5%
0.5%
0.5%
0.3%
0.3%
LOAD REGULATION
2.0%
2.0%
1.5%
0.8%
0.8%
SETUP, RISE TIME
2500ms, 100ms/230VAC 2500ms, 100ms/115VAC at full load
HOLD UP TIME (Typ.)
50ms/230VAC 20ms/115VAC at full load
24V
4.5A
0 ~ 4.5A
108W
150mVp-p
22.8 ~ 28.8V
1.5%
0.2%
0.5%
36V
2.9A
0 ~ 2.9A
104.4W
200mVp-p
34.2 ~ 39.6V
1.5%
0.2%
0.5%
48V
2.2A
0 ~ 2.2A
105.6W
240mVp-p
45.6 ~ 55.2V
1.5%
0.2%
0.5%
VOLTAGE RANGE Note.5 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
PF>0.95/230VAC PF>0.98/115VAC at full load
INPUT EFFICIENCY (Typ.)
78%
83%
84%
87.5%
88%
88.5%
89%
90%
AC CURRENT (Typ.)
1.2A/115VAC 0.6A/230VAC
INRUSH CURRENT (Typ.) 35A/115VAC 65A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
105 ~ 135% rated output power
Protection type : Constant current limiting for Vo=50 ~ 100% of rated voltage, recovers automatically after fault condition is removed
PROTECTION OVER VOLTAGE
3.96 ~ 4.62V 6 ~ 7V
9.4 ~ 10.9V 14.4 ~ 16.8V 18.8 ~ 21.8V 30 ~ 34.8V
Protection type : Shut down o/p voltage, re-power on to recover
41.4 ~ 48.6V 57.6 ~ 67.2V
OVER TEMPERATURE
90 (3.3V ~ 7.5V) , 85 (12V ~ 48V) (TSW1 : detect on heatsink Q101 of power transistor)(optional)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
FUNCTION REMOTE CONTROL
RC+/RC- : 0 ~ 0.8V= power on ; 4 ~ 10V = power off
WORKING TEMP.
-40 ~ +60 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -40 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.04%/ (0 ~ 50
VIBRATION
10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
EMI CONDUCTION & RADIATION Compliance to EN55022 (CISPR22) Class B
HARMONIC CURRENT
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2, heavy industry level, criteria A
MTBF
295.7K hrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
PACKING
159*97*38mm (L*W*H)
0.38Kg; 24pcs/ 10.1Kg/0.76CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:HRP-100-SPEC 2010-11-29