English
Language : 

DRP-480_09 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 480W Single Output Industrial DIN RAIL with PFC Function
480W Single Output Industrial DIN RAIL with PFC Function
DRP-480 series
Features :
Built-in passive PFC function compliance to EN61000-3-2
High efficiency 89% and low dissipation
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Built-in constant current limiting circuit
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
SPECIFICATION
MODEL
DRP-480-24
DRP-480-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
RIPPLE & NOISE (max.) Note.2 120mVp-p
120mVp-p
OUTPUT
VOLTAGE ADJ. RANGE
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
48 ~ 53V
1.0%
0.5%
LOAD REGULATION
1.0%
1.0%
SETUP, RISE TIME
1200ms, 40ms/230VAC at full load
HOLD UP TIME (Typ.)
16ms/230VAC at full load
VOLTAGE RANGE
FREQUENCY RANGE
POWER FACTOR (Typ.)
180 ~ 264VAC
47 ~ 63Hz
0.7
250 ~ 370VDC
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
89%
4A/230VAC
COLD START 40A/230VAC
LEAKAGE CURRENT
<3.5mA / 240VAC
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
30 ~ 36V
54 ~ 60V
Protection type : Shut down o/p voltage, re-power on to recover
100 5 (TSW : detect on heatsink of power switch)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
-20 ~ +70 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
OTHERS
NOTE
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
180.9Khrs min. MIL-HDBK-217F (25 )
DIMENSION
227*125.2*100mm (W*H*D)
PACKING
2.4Kg; 6pcs/15Kg/1.75CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DRP-480-SPEC 2009-08-24