English
Language : 

DRP-240_10 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 240W Single Output Industrial DIN RAIL Power Supply
D R P - 2 4 0 240W Single Output Industrial DIN RAIL Power Supply
series
Features :
Universal AC input / Full range
Built in active PFC function
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 100KHz
3 years warranty
SPECIFICATION
MODEL
DRP-240-24
DRP-240-48
DC VOLTAGE
24V
48V
RATED CURRENT
10A
5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
RATED POWER
240W
240W
RIPPLE & NOISE (max.) Note.2 80mVp-p
150mVp-p
OUTPUT
VOLTAGE ADJ. RANGE
24 ~ 28V
VOLTAGE TOLERANCE Note.3 1.0%
LINE REGULATION
0.5%
48 ~ 53V
1.0%
0.5%
LOAD REGULATION
1.0%
1.0%
SETUP, RISE TIME
800ms, 40ms/230VAC 800ms, 40ms/115VAC at full load
HOLD UP TIME (Typ.)
24ms/230VAC 24ms/115VAC at full load
VOLTAGE RANGE Note.5 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
INPUT
POWER FACTOR (Typ.)
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
0.96/230VAC 0.99/115VAC at full load
84%
85%
2.8A/115VAC 1.4A/230VAC
COLD START 27A/115VAC 45A/230VAC
<3.5mA / 240VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
30 ~ 36V
54 ~ 60V
Protection type : Shut down o/p voltage, re-power on to recover
100 5 (TSW1)detect on heat sink of power transistor
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
-10 ~ +70 (Refer to output load derating curve)
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY &
EMC
(Note 4)
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
UL508, UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
OTHERS
NOTE
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
289.9Khrs min. MIL-HDBK-217F (25 )
DIMENSION
125.5*125.2*100mm (W*H*D)
PACKING
1.2Kg; 12pcs/15.5Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
File Name:DRP-240-SPEC 2010-09-24