DRH-120_11 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 120W Single Output Industrial DIN RAIL Power Supply
120W Single Output Industrial DIN RAIL Power Supply
DR-120 series
Features :
AC input range selectable by switch
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 55KHz
3 years warranty
SPECIFICATION
MODEL
DR-120-12
DR-120-24
DR-120-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
10A
5A
2.5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
0 ~ 2.5A
RATED POWER
120W
120W
120W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
100mVp-p
OUTPUT
VOLTAGE ADJ. RANGE
12 ~ 14V
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
0.5%
24 ~ 28V
1.0%
0.5%
48 ~ 53V
1.0%
0.5%
LOAD REGULATION
1.0%
1.0%
1.0%
SETUP, RISE TIME
500ms, 70ms/230VAC 500ms, 70ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
36ms/230VAC 32ms/115VAC at full load
88 ~ 132VAC/176 ~ 264VAC by switch 248 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
INPUT
EFFICIENCY (Typ.)
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVERLOAD
PROTECTION OVER VOLTAGE
OVER TEMPERATURE
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY & WITHSTAND VOLTAGE
EMC
ISOLATION RESISTANCE
(Note 4) EMC EMISSION
80%
84%
85%
2.6A/115VAC 1.6A/230VAC
COLD START 20A/115VAC 40A/230VAC
<3.5mA / 240VAC
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
15 ~ 16.5V
29 ~ 33V
58 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
85 5 (TSW1)
90 5 (TSW1)
90 5 (TSW1)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-10 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55011,EN55022 (CISPR22) Class B, EN61000-3-2,-3
OTHERS
NOTE
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
136.8Khrs min. MIL-HDBK-217F (25 )
DIMENSION
65.5*125.2*100mm (W*H*D)
PACKING
0.79Kg; 20pcs/16.5Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DR-120-SPEC 2011-06-17