English
Language : 

DR-120 Datasheet, PDF (1/2 Pages) Total Power International – 120W Single Output Industrial DIN RAIL Power Supply
120W Single Output Industrial DIN RAIL Power Supply
DR-120 series
Features :
AC input range selectable by switch
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 55KHz
3 years warranty
SPECIFICATION
MODEL
DR-120-12
DR-120-24
DR-120-48
DC VOLTAGE
12V
24V
48V
RATED CURRENT
10A
5A
2.5A
CURRENT RANGE
0 ~ 10A
0 ~ 5A
0 ~ 2.5A
RATED POWER
120W
120W
120W
RIPPLE & NOISE (max.) Note.2 80mVp-p
80mVp-p
100mVp-p
OUTPUT
VOLTAGE ADJ. RANGE
12 ~ 14V
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
0.5%
24 ~ 28V
1.0%
0.5%
48 ~ 53V
1.0%
0.5%
LOAD REGULATION
1.0%
1.0%
1.0%
SETUP, RISE TIME
500ms, 70ms/230VAC 500ms, 70ms/115VAC at full load
HOLD UP TIME (Typ.)
VOLTAGE RANGE
36ms/230VAC 32ms/115VAC at full load
88 ~ 132VAC/176 ~ 264VAC by switch 248 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
EFFICIENCY (Typ.)
80%
84%
85%
INPUT
AC CURRENT (Typ.)
2.6A/115VAC 1.6A/230VAC
INRUSH CURRENT (Typ.) COLD START 20A/115VAC 40A/230VAC
LEAKAGE CURRENT
<3.5mA / 240VAC
OVERLOAD
105 ~ 150% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
PROTECTION OVER VOLTAGE
15 ~ 16.5V
29 ~ 33V
Protection type : Shut down o/p voltage, re-power on to recover
58 ~ 65V
OVER TEMPERATURE
85 5 (TSW1)
90 5 (TSW1)
90 5 (TSW1)
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
WORKING TEMP.
-10 ~ +60 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0 ~ 50
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
SAFETY STANDARDS
UL508, UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms/500VDC
Compliance to EN55011,EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
OTHERS
NOTE
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, ENV50204, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A
MTBF
136.8Khrs min. MIL-HDBK-217F (25 )
DIMENSION
65.5*125.2*100mm (W*H*D)
PACKING
0.79Kg; 20pcs/16.5Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
File Name:DR-120-SPEC 2008-04-07