English
Language : 

ADD-155B Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 155W Dual Output with Battery Charger(UPS Function)
A D D - 1 5 5 155W Dual Output with Battery Charger(UPS Function)
series
Features :
Universal AC input / Full range
Built-in active PFC function
Protections: Short circuit / Overload / Over voltage
Battery low/battery polarity protections
Cooling by free air convection
100% full load burn-in test
Fixed switching frequency at PFC 67KHz, PWM 134KHz
2 years warranty
SPECIFICATION
MODEL
ADD-155A
ADD-155B
ADD-155C
OUTPUT NUMBER
CH1
CH2
CH3
CH1
CH2
CH3
CH1
CH2
CH3
DC VOLTAGE
13.8V
5V
13.3V
27.6V
5V
27.1V
54V
5V
53.5V
RATED CURRENT
9.5A
3A
0.5A
4.5A
3A
0.5A
2.3A
3A
0.2A
CURRENT RANGE
0 ~ 10.5A 0 ~ 3A
--------
0 ~ 5A
0 ~ 3A
--------
0 ~ 2.5A 0 ~ 3A
--------
RATED POWER
152.75W
152.75W
149.9W
RIPPLE & NOISE (max.) Note.2 150mVp-p 100mVp-p --------
OUTPUT
VOLTAGE ADJ. RANGE
CH1: 12 ~ 14.5V
200mVp-p 100mVp-p --------
CH1: 24 ~ 29V
240mVp-p 100mVp-p --------
CH1: 48 ~ 58V
VOLTAGE TOLERANCE Note.3 2.0%
3.0%
--------
1.0%
3.0%
--------
1.0%
5.0%
--------
LINE REGULATION
1.0%
0.5%
--------
1.0%
0.5%
--------
1.0%
0.5%
--------
LOAD REGULATION
1.0%
2.0%
--------
1.0%
2.0%
--------
1.0%
2.0%
--------
SETUP, RISE TIME
1000ms, 90ms/230VAC 2000ms, 90ms/115VAC at full load
HOLD UP TIME (Typ.)
24ms/230VAC 20ms/115VAC at full load
VOLTAGE RANGE
88 ~ 264VAC 124 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
PF>0.92 at full load
INPUT
EFFICIENCY (Typ.)
78%
81%
81%
AC CURRENT (Typ.)
2.5A/115VAC 1.5A/230VAC
INRUSH CURRENT (Typ.) COLD START 20A/115VAC 40A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
PROTECTION
OVER VOLTAGE
CH1,CH2:105 ~ 135% CH3:0.51 ~ 0.9A rated output power
Protection type : AC Charging Mode : Constant current limiting, recovers automatically after fault condition is removed
UPS Mode : Protected by internal fuse
CH1:15.87 ~ 18.63V
CH1:31.74 ~ 37.26V
CH1:62.1 ~ 72.9V
Protection type : Shut down o/p voltage, re-power on to recover
BATTERY LOW
10V 0.8V
19.5V(+1.5V,-1V )
39V 2V
WORKING TEMP.
-10 ~ +60 (Refer to output load derating curve)
WORKING HUMIDITY
20 ~ 90% RH non-condensing
ENVIRONMENT STORAGE TEMP., HUMIDITY -20 ~ +85 , 10 ~ 95% RH
TEMP. COEFFICIENT
0.03%/ (0 ~ 50 ) on +5V output
VIBRATION
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY STANDARDS
UL60950-1, TUV EN60950-1 approved
SAFETY &
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMI CONDUCTION & RADIATION
HARMONIC CURRENT
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B
Compliance to EN61000-3-2,-3
EMS IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11; ENV50204, EN55024, light industry level, criteria A
MTBF
164.2K hrs min. MIL-HDBK-217F (25 )
OTHERS DIMENSION
199*110*50mm (L*W*H)
PACKING
1Kg; 16pcs/16Kg/0.95CUFT
NOTE
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:ADD-155-SPEC 2010-11-29