English
Language : 

AD-155_11 Datasheet, PDF (1/2 Pages) Mean Well Enterprises Co., Ltd. – 155W SINGLE OUTPUT WITH BATTERY CHARGER(UPS FUNCTION)
A D - 1 5 5 155W Single Output with Battery Charger(UPS Function)
series
Features :
Universal AC input / Full range
Protections: Short circuit / Overload / Over voltage
Battery low and battery polarity protection
Cooling by free air convection
100% full load burn-in test
Fixed switching frequency at PFC 67KHz, PWM 134KHz
2 years warranty
SPECIFICATION
MODEL
AD-155A
AD-155B
AD-155C
OUTPUT NUMBER
CH1
CH2
CH1
CH2
CH1
CH2
DC VOLTAGE
13.8V
13.3V
27.6V
27.1V
54V
53.5V
RATED CURRENT
10.5A
0.5A
5A
0.5A
2.7A
0.2A
CURRENT RANGE
0 ~ 11.5A
0 ~ 0.5A
0 ~ 5.5A
0 ~ 0.5A
0 ~ 2.7A
0 ~ 0.5A
OUTPUT
RATED POWER
151.55W
RIPPLE & NOISE (max.) Note.2 150mVp-p
VOLTAGE ADJ. RANGE
CH1: 12 ~ 14.5V
VOLTAGE TOLERANCE Note.3 2.0%
LINE REGULATION
0.5%
--------
--------
--------
151.55W
150mVp-p
CH1: 24 ~ 29V
1.0%
0.5%
--------
--------
--------
156.5W
240mVp-p
CH1: 48 ~ 58V
1.0%
0.5%
--------
--------
--------
LOAD REGULATION
0.5%
--------
0.5%
--------
0.5%
--------
SETUP, RISE TIME
1000ms, 90ms/230VAC 2000ms, 90ms/115VAC at full load
HOLD UP TIME (Typ.)
24ms/230VAC 20ms/115VAC at full load
VOLTAGE RANGE
88 ~ 264VAC 124 ~ 370VDC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
PF>0.92 at full load
INPUT
EFFICIENCY (Typ.)
80%
84%
84%
AC CURRENT (Typ.)
2.5A/115VAC 1.5A/230VAC
INRUSH CURRENT (Typ.) COLD START 20A/115VAC 40A/230VAC
LEAKAGE CURRENT
<1mA / 240VAC
OVERLOAD
PROTECTION
OVER VOLTAGE
BATTERY LOW
WORKING TEMP.
WORKING HUMIDITY
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
CH1:105 ~ 135% CH2:0.51 ~ 0.9A rated output power
Protection type : AC Charging Mode : Constant current limiting, recovers automatically after fault condition is removed
UPS Mode : Protected by internal fuse
CH1:15.87 ~ 18.63V
CH1:31.74 ~ 37.26V
CH1:62.1 ~ 72.9V
Protection type : Shut down o/p voltage, re-power on to recover
10V 0.8V
19.5V(+1.5V,-1V )
39V 2V
-10 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
0.03%/ (0 ~ 50 )
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes
SAFETY &
EMC
(Note 4)
SAFETY STANDARDS
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
EMC EMISSION
UL60950-1, TUV EN60950-1 approved
I/P-O/P:3KVAC I/P-FG:1.5KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
OTHERS
NOTE
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light industry level, criteria A
MTBF
183.3K hrs min. MIL-HDBK-217F (25 )
DIMENSION
199*110*50mm (L*W*H)
PACKING
0.88Kg; 16pcs/15Kg/0.95CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.”
(as available on http://www.meanwell.com)
File Name:AD-155-SPEC 2011-06-16