English
Language : 

2-1393118-4 Datasheet, PDF (2/5 Pages) Tyco Electronics – KUP Series Panel Plug-in Relay
General Purpose Relays
Industrial Relays
KUP Series Panel Plug-in Relay (Continued)
Potter & Brumfield
Insulation Data
Initial dielectric strength
between open contacts
between contact and coil
between adjacent contacts
Initial insulation resistance
between insulated elements
1200Vrms
2200Vrms
2200Vrms
100MΩ, 500VDC
Other Data
Material compliance: EU RoHS/ELV, China RoHS, REACH, Halogen content
refer to the Product Compliance Support Center at
www.te.com/customersupport/rohssupportcenter
Ambient temperature
DC coil
Enclosed relays, 4 pole: -45ºC to 50ºC
Enclosed relays, 1-3 pole: -45ºC to 70ºC
Open relays: 15ºC higher maximum
AC coil
Enclosed relays, 3 and 4 pole: -45°C to +45°C
Enclosed relays, 1 and 2 pole: -45ºC to +55ºC
Open relays: 15°C higher maximum
Maximum allowable ambient temperature vs voltage (KUP enlcosed)
75°
75°
70°
70°
Other Data (continued)
Category of environmental protection
IEC 61810
RT0 - open relay; RTI - dust protected
Terminal type
Quick connects (QC), .187, .205 or .250;
PCB-THT
Terminal retention, push force
QC .205
17 lbs for 3s
QC .187, QC .250, PCB
25 lbs for 3s
Weight
85g
Packaging/unit tray/25 pcs., box/150pcs.
Accessories
For details see datasheet
Sockets and Accessories, KUP Relays
Product Code Description
27E893
DIN socket (use 20C318 clip)
27E121
Track mount socket (use 20C314 clips)
27E043
Chassis mount/solder eyelet socket (use 20C254 clip)
27E046
Chassis mount/PCB socket (use 20C254 clip)
27E067
Chassis mount/quick connect socket (use 20C254 clip)
27E396
Snap-in/quick connect socket (use 20C254 clip)
60°
50°
40°
30°
1.8 Watt
1.2 Wa tt
DC Coil
DC
Coil
60°
50°
40°
30°
20°
100 110 120 130 140 150 160
% of Nominal Voltage DC
20°
100 110 120 130 140
% Of Nominal 60 Hz. Voltage
Dimensions
KU bracket type
1.437
.19
(36.50)
(4.8)
.63
(16.0)
2.43 MAX.*
(61.72)
2.33 MAX.**
(59.18)
2.29 MAX.***
(58.17)
(2) #6-32 THREAD
TAPPED HOLES
KU stud type
2.27 MAX.*
(57.7)
2.171 MAX.**
(55.14)
2.125 MAX.***
(53.98)
.218
(5.54)
1.391
(35.33)
.065
(1.65)
.437
(11.10)
1.39 MAX.*
(35.3)
1.29 MAX.**
(32.8)
1.25 MAX.***
(31.8)
Seated Heights For KU (open) Relays
.63
(16.0)
.16
(4.1)
X
X
X
2.27 MAX.*
(57.7)
2.171 MAX.**
(55.14)
2.125 MAX.***
(53.98)
1.391” (35.33mm) for #6-32 stud
with .218” (5.54mm) locating tab.
1.52” (38.6mm) for bracket
with 2-#6 32 tapped holes.
1.282” (32.56mm) for #6-32 tapped core
with .125” (3.18mm) or .218” (5.54mm) locating tab.
2.046” (51.97mm) for relay
with printed circuit terminals.
.031 REF.
(.79)
1.468 MAX.
(37.29)
123
456
.031 REF.
(.79)
STUD TYPE also available with .125” (3.18mm)
tab, as well as without stud and locating tab.
Models without stud have core tapped #6-32
THREAD, .25” (6.4mm) minimum depth.
.109 MAX.
(2.77)
7
8
9
1.282 MAX.
(35.56)
*Dimensions with .250” (6.35mm) terminals.
1.687 MAX.
A
B
(42.85) ** Dimensions with .110” (2.79mm) or .205” (5.21mm) terminals.
*** Dimensions with .187” (4.75mm) terminals.
.31
(7.9)
#6-32
THREAD
.150
TAB WIDTH
(3.81)
Relay front diagrams
Models with 6.35mm
(.250) QC terminals
1.531 MAX.
(38.89)
1
23
4
56
7
9
1.406 MAX.
(35.71)
AB
1-3 pole models with
all other terminals
1.531 MAX.
(38.89)
123
456
7
8
9
1.406 MAX.
(35.71)
A
B
A
4 pole models
1.531 MAX.
(38.89)
11 2 2 3 34
5 6 47 8
9 10 11 12
1.406 MAX.
(35.71)
B
2
08-2011, Rev. 0811
www.te.com
© 2011 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the ‘Definitions’ section.
Datasheets and product data is subject to the
terms of the disclaimer and all chapters of
the ‘Definitions’ section, available at
http://relays.te.com/definitions
Datasheets, product data, ‘Definitions’ sec-
tion, application notes and all specifications