WILMAR™ Protective Relays – WUV/WOV Series
TERMINAL STRIPS
#6 - 32 SCREWS
3.0
Voltage Sensitive Relays
Function: 27/59
• ANSI/IEEE C37.90-1978
• UL file No. E58048
• CSA file No. LR61158
Voltage sensitive relays are available for both AC and
DC applications for over/undervoltage protection.
Combination over/undervoltage relays provide
bandpass capabilities. AC relays are either single or
three-phase type. Three phase models are de-
signed to sense the average of the three phases or
the highest single phase. Voltage trip points are
screwdriver adjustable, and operation is time-de-
layed so that momentary voltage transients will not
cause nuisance tripping.
2
3
3
/4
1 /2
11/64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
40.0
30.0
20.0
10.0
0.0
-10.0
0
Typical Time Curve
Overvoltage Relays
WOV Series
0.05 PA0R.1T NU0.M15 BER0.2SELE0C.25TION0.3
Pick-Up Time Delay
Single
Phase
Three
Phase
PRODUCT SPECIFICATIONS
Part Number
WUV/WOV
Nominal Voltage ............................... 120 VAC to 575 VAC
Phase ................................................ Single or Three
Line Frequency ................................. 50-400 Hz
Pick-up to Drop-out Differential ...... 2.5% maximum
Drop-out Point (u/v models) ........... 70-100% of nominal voltage, screwdriver adjustable
Pick-Up Point (o/v models) ............. 100-125% of nominal voltage, screwdriver adjustable
Output Contacts ............................... One set N.O., One set N.C.
Contact Ratings ................................ 5 amp resistive at 120 VAC or 28 VDC
Operating Temperature Range ........ -20°C to +65°C
Power Consumption ........................ 2 VA maximum
Time Delay ........................................ 150-300 ms (UV Model)
Minimum Life ................................... 500,000 operations
Notes:
1. Remove black screw for access to the voltage trip adjustment.
2. Clockwise rotation of the adjustment potentiometer will raise the voltage trip point.
PART NUMBER SELECTION
Sample Part No.
WUV-1-120
Type:
WUV - Undervoltage
WOV - Overvoltage
No. Phases
1 = Single
3 = Three
Line Voltage VAC
120
416
208
440
220
460
230
480
240
525
380
575
Options
P - Transient Protection
A - Two Normally Open Contacts
B - Two Normally Closed Contacts
H - 125VDC, 3A Contacts
Transient Protection - All voltage relays will withstand
momentary voltage surges of twice the nominal rated
input voltage (standard).
Option "P" provides additional transient protection
which complies with the requirements of ANSI/IEEE