English
Language : 

SR2M_09 Datasheet, PDF (1/3 Pages) Tyco Electronics – Safety Relay SR2M
General Purpose Relays
Safety Relay SR2M
SCHRACK
n 2 pole safety relay with either 1NO+1NC or 2CO contacts
n Forcibly guided contacts according to EN 50205
n Rated current 6 A
n 6 kV surge resistance between poles
Applications
Emergency shut-off, machine control, elevator and escalator
control, light barrier control
F0188-D
Approvals
V Z T REG.-Nr. 116064,
E214024,
968/EZ 111.03/05
Technical data of approved types on request
Contact data
Contact configuration
1 NO contact and 1 NC contact
or
2 CO contacts1)
Contact set
single contact, forcibly guided
1 NC + 1NO: type A according to EN 50205
2 CO: type B according to EN 50205
Type of interruption
micro disconnection
Rated voltage / max. switching voltage AC
250 / 400 VAC
Rated current
6A
Maximum breaking capacity AC
1500 VA
Contact material
AgNi
Minimum contact load
10 mA / 5 V
Contact resistance
w 100 mOhm / 1 A / 24 VDC
w 20 Ohm / 10 mA / 5 VDC
Rated frequency of operation with / without load
6 min-1 / 300 min-1
1) According EN50205 only 1NO / 1NC (11-14 and 22-21 or 12-11 and 21-24) shall be used as forcibly
guided contacts.
Contact ratings
Type
Contact Load*)
UL 508
V23047-A1…-A501
V23047-A1…-A501
V23047-A1…-A511
V23047-A1…-A511
*) load on one pole
1 NO
1 NO
1 NO
1 NO
B300 pilot duty
R300 pilot duty
B300 pilot duty
R300 pilot duty
Coil data
Rated coil voltage range DC coil
Operative range to IEC 61810
Coil versions, DC-coil
Coil
Rated
code
voltage
VDC
005
5
006
6
009
9
012
12
015
15
018
18
021
21
024
24
036
36
Operate
voltage
VDC
3.8
4.5
6.8
9.0
11.3
13.5
15.8
18.0
27.0
Release
voltage
VDC
0.5
0.6
0.9
1.2
1.5
1.8
2.1
2.4
3.6
Ambient
temp. [°C]
40°C
40°C
40°C
40°C
Cycles
6x103
6x103
6x103
6x103
5...110 VDC
2
Coil
resistance
Ohm
35,7+10%
51+10%
116+10%
206+10%
321+10%
483+10%
630+10%
823+10%
1851+10%
Rated coil
power
mW
700
706
698
699
700
671
700
700
700
Datasheet Rev. IJ1
Issued 2009/10
www.tycoelectronics.com
www.schrackrelays.com
1
Dimensions are in mm unless Product specification
processing information only in the ‘Schrack’ section.
otherwise specified and are
according to IEC 61810-1.
to be used together with the
shown for reference purposes Product data, technical para- 'Definitions' section in the cat- Specifications subject to
only.
meters, test conditions and
alogue or at schrackrelays.com change.