English
Language : 

MRI2030 Datasheet, PDF (1/4 Pages) Tyco Electronics – MRI 2030 High Performance (100dB 100 kHZ to 10 GHz)
Corcom Facility EMI Filters Product Guide
Catalog: 1654986
Issue Date: 06.2011
MRI 2030 High Performance (100dB 100 kHZ to 10 GHz)
MRI2030
Features
• UL 1283 listed
• Filter compartment sealed, constructed of suitably
plated or stainless steel
• Removable input cover for terminal access and field
wiring connection
• Threaded conduit fitting with flexible lead on the load
side
• Knockouts provided on the input side
• Discharge bleeder resistor provided to reduce shock
hazard
Electrical Characteristics
Rated Voltage:
277/480 VAC 50/60 Hz
Rated Current:
2 x 30A
Voltage Drop:
Less than 1% @ unity power factor.
Overload:
140% of rated current for 15 minutes.
Harmonic Distortion:
Less than 2% @ full rated current.
Dielectric Withstanding Voltage:
Per MIL-PRF-15733 and UL1283.
D.C. Insulation Resistance:
Per MIL-STD-202, Method 302.
Terminal Strength:
Per MIL-STD-202, Method 211, Condition E.
Temperature Rise:
Per MIL-PRF-15733 and UL1283.
R.F. Radiation:
100 dB minimum shielding effectiveness.
Insertion Loss:
100 dB 100 kHz to 10GHz.
32
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
USA Cust. Svc.: 1-800-468-2023
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
Corcom Prods: 1-847-680-7400
te.com