|
CDEUX Datasheet, PDF (1/2 Pages) Tyco Electronics – CDEUX Series - Extended Range Buffer Networks (Capacitive Input) | |||
|
Corcom Facility EMI Filters Product Guide
Catalog: 1654986
Issue Date: 11.2009
CDEUX Series - Extended Range Buï¬er Networks (Capacitive Input)
CDEUX Series
Filter Cabinet
⢠Modiï¬ed NEMA I, constructed of not less than #14
gauge CRS with galvanized bulkhead
⢠Blue epoxy ï¬nish to all non-conductive surfaces
⢠R.F. Radiation of the shielded (load) compartment
greater than 100 dB from 14 kHz to 10 GHz
⢠Front cover access, dual cover design
⢠Filter inserts pre-wired to standoffs and lugs
⢠Lifting hooks and mounting tabs
⢠Legs for ï¬oor mount available (see page 24)
6P16 â
Individual Filters
⢠Sealed components with welded and/or soldered
seams
⢠Constructed of not less than #16 gauge steel with
corrosion resistant plating
⢠Bleeder resistor to eliminate shock hazard provided
⢠Surge arrestors provided upon requestâ¡
Electrical Characteristics
Voltage Drop:
Less than 1% @ unity power factor
Overload:
140% of rated current for 15 minutes
Harmonic Distortion:
Less than 2% @ full rated current
Dielectric Withstanding Voltage:
Per MIL-PRF-15733 and UL1283
D.C. Insulation Resistance:
Per MIL-STD-202, Method 302
Terminal Strength:
Per MIL-STD-202, Method 211, Condition E
Temperature Rise:
Per MIL-PRF-15733 and UL1283
R.F. Radiation:
100 dB minimum shielding eï¬ectiveness
Insertion Loss:
100 dB from 14 kHz - 10 GHz per MIL-STD-220A, under
load condition, using extended range buï¬er networks
over the frequency range of 14 kHz - 20 MHz
Applicable Publications:
MIL-PRF-15733 â Filters, radio interference
MIL-STD-202 â Test methods for Components
MIL-STD-220A â Test method of Insertion Loss
MIL-STD-285 â Test method for Shielding Eï¬ectiveness
NFPA 70-1987 â National Electric Code
486A - 1983 â Wire Connectors and Lug
UL1283 â Underwriter Laboratories
How to Order:
Shown with optional legs
CDEUX 4 01000 A6 -S -L
Legs
Surge Arrestors (optional) 1
Voltage/Frequency
A6 - 120/208V, 60Hz
B6 - 277/480V, 60Hz
A4 - 120/208V, 400Hz
Current Rating 2
# of Filters
Examples:
Series
CDEUX401000A6-S-L =
4, 1000A CDEUX, 120/280V ï¬lters in cabinet
with surge arrestors and legs
CDEUX300030B6 =
3, 30A CDEUX, 277/480V ï¬lters in cabinet
Note 1:
Surge Arrestor for A6/A4* Models: V251BA60
Surge Arrestor for B6 Models: V481BA60
Note 2: Current conï¬guration listed as 5 digits with leading zeros
â¡ Not intended for HEMP applications. Refer to the CDEUL(<150A)
page 12 or TECUL Series (>225A) page 14 for HEMP applications..
â 60 Hz Models Only
10
Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric
USA Cust. Svc.: 1-800-468-2023 www.tycoelectronics.com
equivalents. Dimensions are shown for reference purposes only. Specifications subject to change.
Corcom Prods: 1-847-680-7400
www.corcom.com
|
▷ |