English
Language : 

CDB-38-70001 Datasheet, PDF (1/2 Pages) Tyco Electronics – CMOS IC Time Delay Relay
Catalog 1308242
Issued 3-03
P&B
Timing Modes
Delay on operate – Delay period begins when input voltage is applied. At
the end of the delay period, the relay will operate and will not release until
input voltage is removed. Reset occurs when input voltage is reapplied.
INPUT
ON
VOLTAGE OFF
N.O. RELAY ON
CONTACTS OFF
TIME
➛
Delay on release – Input voltage must be applied continuously to operate
the internal relay. When control Input is applied, the relay energizes.
When control input is removed, timing begins. When timing is complete,
the relay will de-energize. Time may be reset to zero during timing by
reapplying control input.
CONTROL ON
INPUT
OFF
N.O. RELAY ON
CONTACTS OFF
TIME
➛
Timing Specifications
Timing Ranges: From 0.1 to 180 sec.
Timing Adjustment: Fixed, external resistor and knob adjustable.
Tolerance (for AC units add ±1/2 cycle 60 Hz.):
Knob Adj. Types: ± 5% of max. specified at high end of timing range; min.
specified, or less, at low end; ± 10% full scale.
Fixed Types: ± 5%.
Res. Adj. Types: ± 5% at high end of timing range; min. specified, or less,
at low end.
Delta Time (for AC units add ±1 cycle 60 Hz.): ± 5%.
Repeatability (for AC units add ±1 cycle 60 Hz.): ± 1%.
Release Time: 45 ms, typ.; 60 ms, max.
Recycle Time: 45 ms, typ.; 60 ms, max.
CD series
CMOS IC Time Delay Relay
• 1% Repeatability
• Operates from -40°C to +55°C
• Delay on operate or delay on release timing modes
• Fixed, knob or resistor adjustable types
– Calibrated dial on knob adjustable types
• 10A output relay with SPDT or DPDT contacts
• Various models time from 0.1 to 180 sec.
File E22575
File LR15734
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that user also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Initial Dielectric Strength
Between Open Contacts: 500V rms, 60 Hz.
Between All Other Conductors: 500V rms, 60 Hz.
Input Data @ 25°C
Voltage: 24 & 120VAC and 12 through 110VDC.
Power Requirement: AC Types: Typically less than 3 VA.
DC Types: Typically less than 3 W.
Transient Protection: Yes.
Reverse Voltage Protection: Yes.
Input Voltages & Limits @ 25°C
Voltage
Type
Nominal
Voltage
Minimum
Voltage
Maximum
Voltage
AC
24
20
28
120
105
130
12
DC
24
48
110
11
13
20
32
41
55
95
125
Note: DC voltage must be filtered (5% p-p ripple max. at nom. voltage).
AC models will operate on 50 or 60 Hz.
Environmental Data
Temperature Range: Storage: -55°C to +85°C.
Operating: -40°C to +55°C.
Contact Data @ 25°C
Arrangements: 2 Form C (DPDT).
Material: Silver-cadmium oxide alloy.
Rating: 10A @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC; 1/3 HP @
120VAC.
Expected Mechanical Life: 10 million operations.
Expected Electrical Life: 100,000 operations, min., at rated load.
Dimensions are shown for
1222 reference purposes only.
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Mechanical Data
Termination: 8- or 11-pin octal style plug.
Enclosure: Yellow plastic case. Knob adjustable types have dial scale
calibrated in seconds ± 5%.
Sockets: Models with 8-pin base fit either 27E122 or 27E891 (snap-on)
screw terminal sockets. 11-pin types fit either 27E123 or
27E892 (snap-on) screw terminal sockets.
Weight: 8 oz. (227g) approximately.
Specifications and availability
subject to change.
www.tycoelectronics.com
Technical support:
Refer to inside back cover.