English
Language : 

96-3100 Datasheet, PDF (1/2 Pages) Tyco Electronics – Definite Purpose Contactor 1- or 2-pole, 20-40 FLA AC Coil
Catalog 1308242
Issued 3-03
PRODUCTS UNLIMITED
Features
• Robust 1- and 2-pole contactors.
• Shunt available on 1-pole models.
• Convenient mounting plate.
Model 96 - 3100 series
Definite Purpose Contactor
1- or 2-pole, 20-40 FLA
AC Coil
File E75492
File EN60947-4-1:1991
IEC 947-4-1
Users should thoroughly review the technical data before selecting a product part
number. It is recommended that users also seek out the pertinent approvals files of
the agencies/laboratories and review them to ensure the product meets the
requirements for a given application.
Environmental Data
Temperature Range: Storage and Operating: -40°C – +65°C.
Flammability: UL 94-HB housing.
Contact Data @ 25°C
Arrangements: 1 Form X (SPST-NO-DM) with or without shunt and
2 Form X (DPST-NO-DM).
Maximum Ratings: See Contact Ratings Table.
Material: Silver Cadmium Oxide.
Coil Data @ 25°C
Voltage: 24 - 277 VAC, 50/60 Hz. See Coil Data Table below.
Insulation Class: UL Class B (130°C).
Duty Cycle: Continuous.
Mechanical Data
Contact Termination:
20, 25, 30 FLA Models
Type: #10-32 Screw with quad 0.250” (6.35 mm) quick connects.
Wire Size: 16-8 AWG (Stranding must be split for 8 AWG wire.)
Tightening Torque: 25 in.-lbs.
40 FLA Models
Type: Box Lug with dual 0.250” (6.35 mm) quick connects.
Wire Size: 14-4 Cu/Al AWG
Tightening Torque: 40 in.-lbs.
Coil Termination: Dual 0.250” (6.35 mm) quick connects.
Arc Cover: Optional on 20-30 FLA models, standard on 40 FLA models.
Weight: One Pole Types: 8 oz. (227 g) approximately.
Two Pole Types: 9.6 oz. (273 g) approximately
Contact Ratings
Full
Load
Amps
20
Number
of
Poles
2
25
1
25
2
30
1
30
2
40
1
40
2
Coil Data
Nominal Coil Voltage
Maximum Pickup Volts
Drop-Out Volts Range
Nominal Inrush VA @ 50 Hz
Nominal Inrush VA @ 60 Hz
Nominal Sealed VA @ 50 Hz
Nominal Sealed VA @ 60 Hz
Nominal DC Resistance - Ohms
Dimensions are shown for
830 reference purposes only.
Line
Voltage
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
240/277
480
600
Locked
Rotor
Amps
120
100
80
150
50
40
150
125
100
150
75
50
150
125
100
240
200
160
240
200
160
Resistive
Amps
Rating
30
30
30
30
30
30
35
35
35
40
40
40
40
40
40
50
50
50
50
50
50
Maximum Horsepower
Voltage
Single
Phase
120
2
240
3
120
1
240
2
120
2
240
3
120
1
240
2
120
2
240
3
120
2
240
3
120
2
240
3
24
18
6 - 15
22.5
20
7
5.25
16.5
1-Pole Models
120
88
20 - 70
22.5
20
7
5.25
420
208/240
177
40 - 140
22.5
20
7
5.25
1850
277
221
50 - 165
22.5
20
7
5.25
2650
24
18
6 - 15
37
35
8
7
11
2-Pole Models
120
88
20 - 70
37
35
8
7
250
Dimensions are in inches over
(millimeters) unless otherwise
specified.
Specifications and availability
subject to change.
208/240
177
40 - 140
37
35
8
7
1000
277
221
50 - 165
37
35
8
7
1600
www.tycoelectronics.com
Technical support:
Refer to inside back cover.