English
Language : 

408-1826 Datasheet, PDF (1/4 Pages) Tyco Electronics – Reasons for reissue are given in Section 7, REVISION SUMMARY.
Post-Insulated STRATO-THERM*
Terminal and Splice Die Assemblies
Instruction Sheet
408-1826
22 JAN 09 Rev E
Upper Die
(Stationary)
Crimping
Chamber
Reasons for reissue are given in Section 7,
REVISION SUMMARY.
2. DESCRIPTION (Figure 1)
Each die assembly consists of an upper die
(stationary) and a lower die (moving), each marked
with the wire size. When mated, the dies form the
crimping chamber. Each die is held in the crimping
head by a single screw.
3. DIE ASSEMBLY INSTALLATION AND REMOVAL
Lower Die
(Moving)
DYNA-CRIMP
Crimping Head
69099 (Ref)
Figure 1
3.1. Installation
Before installing the die assembly, install the crimping
head onto the power unit as described in Instruction
Sheets 408–2458 or 408–8959, and Customer
Manuals 409–1950 or 409–10081.
DANGER
To avoid personal injury, exercise extreme
caution when using the power unit. Avoid
depressing the foot switch or trigger control when
installing or removing die assembly.
1. Loosen the setscrew in the top of the crimping
head and insert shank on upper die, making sure
that the shank is facing the setscrew. Refer to
Figure 2. Tighten setscrew just enough to hold die
in place.
2. Activate the power unit by depressing the foot
switch or trigger control with short, quick strokes.
Advance the ram until the setscrew in the ram is
visible.
1. INTRODUCTION
Post–Insulated STRATO–THERM Terminal
and Splice Die Assemblies 69211–[ ], 69212–[ ],
69213–[ ], 69214–[ ], 69215–[ ], and 69254–[ ] are
used in conjunction with DYNA–CRIMP* Crimping
Head 69099 or 1752868–1 and Hydraulic Power Unit
69120–[ ] or 1804700–[ ] to crimp the insulating
sleeve of Post–Insulated STRATO–THERM Terminals
and Splices. The die assembly is selected according
to the wire size being used.
Refer to Instruction Sheets 408–2458 or 408–8959
(supplied with crimping head) and Customer Manuals
409–1950 or 409–10081 (supplied with power unit) for
tooling information. Product part number information
is available in Catalog 82011.
Align Lower Die
with Upper Die,
Slide Lower Die
In and Center
Shank Over
Ram Well
Ram
Setscrew
Setscrew
Flat on
Shank
Ram Well
NOTE
i
All dimensions on this document are in
millimeters [with inches in brackets]. Figures and
illustrations are for reference only and are not
drawn to scale.
Figure 2
E2009 Tyco Electronics Corporation, Harrisburg, PA
TOOLING ASSISTANCE CENTER 1-800-722-1111
All International Rights Reserved
PRODUCT INFORMATION 1-800-522-6752
TE logo and Tyco Electronics are trademarks.
*Trademark. Other products, logos, and company names used are the property of their respective owners.
This controlled document is subject to change.
For latest revision and Regional Customer Service,
visit our website at www.tycoelectronics.com
1 of 4
LOC B