25-000 Datasheet, PDF (1/1 Pages) Tyco Electronics – WILMAR™ Protective Relays - 25-000 Series
WILMAR™ Protective Relays – 25-000 Series
#6 - 32 STUDS
6 PLACES
4 1/2
3 13/16
Frequency Sensitive Relays
Function: 81 O/U
• ANSI/IEEE C37.90-1978
The output contacts of frequency relays are ener-
gized when the frequency exceeds the adjustable set
point. Overfrequency and underfrequency relays are
available in 50, 60 and 400Hz. Combination over/
underfrequency “band pass” relays are also avail-
able. These are energized at rated frequency and de-
energized during overfrequency or underfrequency
conditions. Frequency Differential relays are ener-
gized above the preset frequency. The pick-up and
drop-out frequency settings are independently ad-
justable.
Operation:
The normally open contacts close, and the normally
closed contacts open, at nominal frequency. The
contacts are de-energize at underfrequency,
overfrequency or no input voltage.
3 /4
2 1 /2
3
PART NUMBER SELECTION
/11 64" DIA.
4 MTG. HOLES
Note: Dimensions in inches. Multiply values by 25.4 for dimensions in mm.
Part Number
PRODUCT SPECIFICATIONS
25-000 Series
Input Voltage (±10%) ...................... 120 VAC
Frequency Range (adjustable) ........ See Part Number Selection
Trip Points ........................................ Screwdriver adjustable
Temperature Range ......................... -20oC to +85oC
Temperature Drift ............................. ± 1% frequency error over temperature range
Voltage Drift ..................................... ± 1% frequency error input voltage variation of ± 10%
Contact Ratings ................................ 5 Amp resistive at 120 VAC or 28VDC
Output Contacts ............................... One set N.O., One set N.C.
Notes:
1. The contacts are shown in the de-energized position.
2. Remove screws for access to the underfrequency and overfrequency trip adjustments.
3. Clockwise rotation of the adjustment potentiometer will raise the frequency trip points.
PART NUMBER SELECTION
Sample Part No.
25-050X
Type:
25 - Over/Underfrequency
Frequency Range
Under
050 =
40-50 Hz
060 =
50- 60 Hz
400 =
350- 400 Hz
Mounting Options
X = Flange
blank = Stud
Over
50-60 Hz
60-70Hz
400-450Hz
Consult factory for additional models.
42