English
Language : 

2-1415074-1 Datasheet, PDF (1/3 Pages) Tyco Electronics – Relay Package RT
General Purpose Relays
Relay Package RT
n Relay package consisting of RT relay, DIN-rail socket,
plastic retaining clip, module and marking tag
n 1 CO with 16 A or 2 CO with 8 A rated load
n Sensitive DC- or AC coil
n Reinforced insulation (protection class II / VDE 0700),
safe separation to VDE 0160
n Jumper bars for interconnection
n Further accessories see Accessories RT
Approvals
V Z Relay:
REG.-Nr. 6106,
E214025
V Z Socket:
REG.-Nr. 6106,
E135149
Technical data of approved types on request
Contact data
1-pole
2-pole
Contact configuration
1 CO
2 CO
Contact set
single contact
Type of interruption
micro disconnection
Rated voltage / max. switching voltage AC
240 / 400 VAC
Rated current
16 A*)
8A
Limiting continuous current
16 A*)
8 A, UL: 10 A
Maximum breaking capacity AC
4000 VA
2000 VA
Limiting making capacity,max 4 s, df 10%
30 A
15 A
Contact material
AgNi 90/10, AgNi90/10 gold plated
Rated frequency of operation with / without load
6 / 1200 min-1
*) For full load current (16 A) the relay terminals 11-21, 12-22 and 14-24 have to be bridged.
Contact ratings
For contact ratings see datasheet
Interface Power relay RT
Coil data
Rated coil voltage range DC coil
AC coil
Operative range to IEC 61810
24 VDC
24, 115, 230 VAC
2
Coil versions, DC-coil
Coil
Rated
code
voltage
VDC
LC4
24
Operate
voltage
VDC
16.8
Release
voltage
VDC
2.4
Coil
resistance
Ohm
1440+10%
Rated coil
power
mW
400
Coil versions, AC-coil 50Hz
Coil
Rated
Operate
Release
Coil
Rated coil
code
voltage
voltage
voltage
resistance
power
50 Hz
50 Hz
50 Hz
VAC
VAC
VAC
Ohm
VA
R24
24
18.0
3.6
350+10%
0.76
S15
115
86.3
17.3
8100+15%
0.76
T30
230
172.5
34.5
32500+15%
0.74
All figures are given for coil without preenergization, at ambient temperature +23°C
Other coil voltages on request
SCHRACK
F0287-C
1
Datasheet Rev. IJ1
Dimensions are in mm unless Product specification
processing information only in the ‘Schrack’ section.
Issued 2009/10
otherwise specified and are
according to IEC 61810-1.
to be used together with the
www.tycoelectronics.com
shown for reference purposes Product data, technical para- 'Definitions' section in the cat- Specifications subject to
www.schrackrelays.com
only.
meters, test conditions and
alogue or at schrackrelays.com change.