2-1393122-4 Datasheet, PDF (1/3 Pages) Tyco Electronics – KHA Series Panel Plug-in Relay | |||
|
General Purpose Relays
Industrial Relays
KHA Series Panel Plug-in Relay
n Compact package
n Two and four pole Form C contact arrangements
n Polycarbonate or nylon dust cover
n Various mounting configurations
n Indicator lamp and push-to-reset options available
n Various contact materials available for specific load requirements
Potter & Brumfield
Typical applications
Industrial sewing/stitching machines, fitness, elevators, pumps, robotics,
solar panels
Approvals
UL E22575; CSA LR15734
Technical data of approved types on request
Contact Data
Contact arrangement 2 form C (2CO), 4 form C (4CO)
Rated voltage
240VAC
Rated current
1-5A
Contact material
Ag, AgCdO, Au-AgNi,
Au overlay Ag, Au diffused Ag
Contact style
Single contact or bifurcated crossbar
Min. recommended contact load
Ag (single contact)
100mA, 12VDC
AgCdO (single contact)
300mA, 12VDC
Au-AgNi (single contact)
10mA, 12VDC
Au overlay Ag (bifurcated crossbar)
Dry circuit
Au diffused Ag (single contact)
50mA, 12VDC
Initial contact resistance
Ag, AdCdO
100mâ¦
Au-AgNi, Au overlay Ag, Au diffused Ag
200mâ¦
Frequency of operation
360 ops./hour
Operate/release time max.
13/6ms
Contact ratings
Type
Load
UL 508
Ag
5A, 120VAC, general purpose
2.5A, 240VAC, general purpose
1/10HP, 120/240VAC
180VA, 250VAC, pilot duty
42VA, 28VDC, pilot duty
AgCdO
5A, 120VAC, general purpose
2.5A, 240VAC, general purpose
1/10HP, 120/240VAC
180VA, 250VAC, pilot duty
42VA, 28VDC, pilot duty
5A, 240VAC, general purpose
5A, 28VDC, resistive
Au-AgNi
2A, 120VAC, resistive
Au overlay Ag 1A, 120VAC
1A, 30VDC
Au diffused Ag 5A, 120VAC, general purpose
2.5A, 240VAC, general purpose
1/10HP, 120/240VAC
180VA, 250VAC, pilot duty
42VA, 28VDC, pilot duty
Cycles
Note: The relay should only carry â¤15A continuously (all poles combined).
Mechanical endurance
10x106 ops.
UC
Coil Data
Coil voltage range
Coil insulation system according UL
5 to 240VDC
6 to 240VAC
Class B
Coil versions, DC coil
Coil
Rated
Operate
ReleaseCoil
Rated coil
code
voltage
voltagevoltage resistance
power
VDC
VDC
â¦Â±10%
mW
5
5
3.75
32
800
6
6
4.5
40
900
12
12
9.0
160
900
24
24
18.0
690
850
48
48
36.0
2600
900
110
110
82.5
11000
1100
220/240 Use 110V relay with series dropping
5W resistor of 11Kâ¦
All figures are given for coil without preenergization, at ambient temperature +23°C.
Coil versions, AC coil
Coil
Rated
Operate
Coil
Rated coil
code
voltage
voltage
resistance
power
VAC
VAC
â¦Â±15%
VA
6
6
5.1
10.5
1.2
12
12
10.2
43
1.2
24
24
20.4
160
1.25
48
48
40.8
668
1.2
120
120
102.0
3900
1.35
240
240
204.0
12000
1.5
All figures are given for coil without preenergization, at ambient temperature +23°C.
Insulation Data
Initial dielectric strength
between open contacts
between contact and coil
between adjacent contacts
between coil and frame
Initial insulation resistance
between insulated elements
1000Vrms
1500Vrms
1500Vrms
1500Vrms
100M⦠at 500VDC
Other Data
Material compliance: EU RoHS/ELV, China RoHS, REACH, Halogen content
refer to the Product Compliance Support Center at
www.te.com/customersupport/rohssupportcenter
Ambient temperature
-45ºC to 70ºC
Category of environmental protection
IEC 61810
RTI - dust protected
08-2011, Rev. 0811
www.te.com
© 2011 Tyco Electronics Corporation,
a TE Connectivity Ltd. company
Datasheets and product specification
according to IEC 61810-1 and to be used
only together with the âDefinitionsâ section.
1
Datasheets and product data is subject to the Datasheets, product data, âDefinitionsâ sec-
terms of the disclaimer and all chapters of
tion, application notes and all specifications
the âDefinitionsâ section, available at
are subject to change.
http://relays.te.com/definitions
|
▷ |