1VK1_11 Datasheet, PDF (1/5 Pages) Tyco Electronics – General Purpose RFI Power Line Filters – Ideal for High Impedance Load | |||
|
K Series
Corcom Product Guide
Catalog: 1654001
Issue Date: 06.2011
General Purpose RFI Power Line Filters â Ideal for High Impedance Load
UL Recognized
CSA Certiï¬ed
VDE Approved**
VK6
VK7 / EK7
1
K Series
⢠Suitable for high impedance loads
⢠Well suited to applications where pulsed,
continuous and/or intermittent RFI interference
is present
⢠EK models meet the very low leakage current
requirements for VDE portable equipment and
non-patient care medical equipment
⢠Available with ground line inductor (choke)
Ordering Information
10 E K 7 M
Suï¬x
M â Metric inserts (style 7 only)
Omit for standard or none
C â Ground choke (30, 40VK6 only)
Input / Output Style
1 â .250 [6.3] spade terminals
3 â Wire leads
6 â Threaded bolt
7 â IEC inlet* (line side)
.250 [6.3] spade terminals
(load side)
K Series
Leakage current designation
E â Low leakage (<0.5 mA)
V â Standard
Current Rating
1, 2, 3, 5, 10, 20, 30, 40 or 60A
VK1 / EK1
VK3 / EK3
Speciï¬cations
Maximum leakage current each Line to Ground:
VK Models
EK Models
@ 120 VAC 60 Hz:
.5 mA
.21 mA
@250 VAC 50 Hz:
1.0 mA
.36 mA
Hipot rating (one minute):
Line to Ground:
Line to Line:
2250 VDC
1450 VDC
Rated Voltage (max):
250 VAC
Operating Frequency:
50/60 Hz
Rated Current:
1 to 60A*
Operating Ambient Temperature Range
(at rated current Ir):
-10°C to +40°C
In an ambient temperature (Ta) higher than +40°C
the
maximum
operating
current (Io)
follows: Io
is calculated as
= Ir ï(85-Ta)/45
Available Part Numbers
1VK1
10VK6
1VK3
10VK7
2VK1
10VK7M
2VK3
20VK1
3VK1
20VK6
3VK3
20VK7*
3VK7
30VK6
3VK7M
30VK6C
5VK1
40VK6
5VK3
40VK6C
5VK7
60VK6
5VK7M
1EK1
10VK1
1EK3
10VK3
2EK1
2EK3
3EK1
3EK3
3EK7
3EK7M
5EK1
5EK3
5EK7
5EK7M
10EK1
10EK3
10EK7
10EK7M
20EK1
*1-15A: IEC 60320-1 C14 inlet mates with C13 connector
20VK7: C20 inlet mates with C19 connector
**20VK7, 20A model tested by Underwriters Laboratories
to US and Canadian requirements and is
VDE approved at 16A, 250VAC
Dimensions are in inches and millimeters unless otherwise speciï¬ed. Values in italics
are metric equivalents. Dimensions are shown for reference purposes only.
Speciï¬cations subject to change.
49